A-22
INSTALLATION
Step 22 – Connections to control panel in leg base
FIGURE A.11
Step 23 - Install Filters (See section D for filter
replacement instructions)
Before opening door, unit must be off and the power
switch on the side of the control panel turned to the off
position.
a. Unlock door handle using the supplied hex tool or any 5/16”
hex wrench, then open door.
FIGURE A.12
b. Unclamp filter handles
FIGURE A.13
c. Install new filters making sure the first filter is pushed fully
against rear of unit. All remaining filters in each row push
against the previous filter flange.
FIGURE A.14
WARNING
Connect green
wire from control
module above
compressed air
tank to this fitting
“Low Side
Pressure Tap”
connect ¼” black
tube from clean
air side (upper
fitting on side of
unit)
“High Side
Pressure Tap”
connect ¼” black
tube from dirty
air side (lower
fitting on side of
unit)
Power feed from
remote control panel
Connect green wire
from remote control
panel (ref wire
schematic)
Models L17587-2, L17587-6, L17587-9,
L17587-11, L17587-14, L17587-18, L17587-21,
L17587-26, L17587-29, L17587-30, L17587-31,
L17587-32, L17587-33, L17587-34, L17587-35
are 4 filters deep.