RANGER 8+ DIESEL
A-7
INSTALLATION
A-7
Connection of RANGER 8+ DIESEL to premises
wiring must be done by a licensed electrician and
must comply with the National Electrical Code and
all other applicable electrical codes.
230 Volt
60 Hz.
3-Wire
Service
POWER
COMPANY
METER
230 VOLT
115 VOLT
115 VOLT
LOAD
N
NEUTRAL
BUS
GROUND
PREMISES
DISCONNECT AND
SERVICE
OVERCURRENT
PROTECTION
GND
N
NOTE: No. 8 COPPER CONDUCTOR CABLE SEE
NATIONAL ELECTRICAL CODE FOR ALTERNATE WIRE
SIZE RECOMMENDATIONS.
230 VOLT
GROUNDED CONDUCTOR
40AMP
230 VOLT
DOUBLE
POLE
CIRCUIT
BREAKER
DOUBLE POLE DOUBLE THROW
SWITCH RATING TO BE THE SAME
AS OR GREATER THAN PREMISES
SERVICE OVERCURRENT
PROTECTION.
50 AMP, 115/230
VOLT PLUG
NEMA TYPE 14-50
50 AMP, 115/230 VOLT
RECEPTACLE
Figure A.1
CONNECTION OF RANGER 8+ DIESEL TO PREMISES WIRING