B-10
OPERATION
B-10
RANGER 8+ DIESEL
115/230 VOLT DUAL VOLTAGE RECEPTACLE
The 115/230 volt receptacle can supply up to 40 amps
of 230 volt power to a two wire circuit, up to 40 amps
of 115 volt power from each side of the three wire cir-
cuit, (up to 80 amps total). Do not connect the 115
volt circuits in parallel. Current sensing for the auto-
matic idle feature is in both legs of the three wire cir-
cuit as shown below.
FIGURE B.3
115V DUPLEX RECEPTACLES
The 115V auxiliary power receptacles should only be
used with three wire grounding type plugs or approved
double insulated tools with two wire plugs.
Maximum Current Draw from 115V Duplex
Receptacles - No Welding
EACH HALF OF
EACH 115V
DUPLEX
TOTAL FROM
ONE 115V
DUPLEX
TOTAL FROM
BOTH 115V
DUPLEXES
LOAD FROM
115 V / 230 V
DUAL VOLTAGE
RECEPTACLE
0
2.2 KW
4.5 KW
6.7 KW
9.0 KW
15 AMPS
15 AMPS
15 AMPS
15 AMPS
0
30 AMPS
30 AMPS
30 AMPS
20 AMPS
0
60 AMPS
60 AMPS
40 AMPS
20 AMPS
0