Low Profile –1600 Series Advantage Digital Service Manual – Int’l
10
Intermittent heating
Thermal overload of main fan
and burner blower motors
The main fan motors and the burner blower motors
are equipped with internal thermal protection and will
cease to operate if overheating occurs. As the motors
overheat and then cool, this will cause the units to
cycle on and off intermittently. Improper ventilation or
lack of preventive maintenance may cause this
problem. Also, most of the problems listed under
“Oven will not heat” can cause intermittent failure.
Power supply
Check for supply voltage at terminals L1 and L2. If
voltage is not present check breakers.
Power switch
Check continuity between switch terminals. Replace
switch as needed.
Fuse, 10 Amp.
Check and/or replace.
Fuse holder
Check and/or replace.
Hi-limit thermostat(s),
control box
Check for voltage on both sides of the switch.
Terminals are normally closed. If open, reset and test
for proper operation. If thermostat will not hold, and
the control box temperature is not exceeding 140
°
F
(60
°
C), replace thermostat.
Relay, oven power
Check for line voltage to the relay coil. If voltage is not
present, trace wiring back to the hi-limit thermostat. If
voltage is present, check to insure contacts are
closing. Replace relay as needed.
Control transformer
Check for line voltage supply to the primary of the
control transformer. If no voltage is present, trace
wiring back to the oven power relay. If voltage is
present, check for 24VAC at the transformer
secondary. If there is primary voltage, but no
secondary voltage, replace control transformer.
Conveyor motor
Check for line voltage supply to the conveyor motor at
wire #28 to neutral. If no voltage is present, trace
wiring back to the oven power relay. If voltage is
present and the motor will not run, check the motor
windings for opens or shorts.
WITH POWER OFF: Check the motor windings as
follows:
Grey to black - 116
Ω
Grey to brown - 116
Ω
Brown to black - 230
Ω
Conveyor will not
run
Capacitor, conveyor motor
Check for shorts or grounds. Replace capacitor as
needed.
WARNING: Capacitor has a stored charge, discharge
before testing.
Switch, conveyor reversing
Check continuity between switch terminals, Replace
switch as needed.
Oven control
If there is supply voltage to the motor. And the motor,
capacitor, and reversing switch check good, replace
the oven control.
NOTE: Display will indicate
“Belt jam”
Conveyor motor
runs, but there is
no speed display
Oven control
Check for output voltage from the oven control to hall
effect sensor (sensor is located in conveyor motor).
Measure voltage at the motor connector, red wire and
yellow wire. Voltage should be approx. 10VDC. If no
voltage is present, trace wiring back to oven control. If
there is no voltage present at the oven control,
replace the oven control.
Summary of Contents for 1633-000-EA
Page 19: ...Low Profile 1600 Series Advantage Digital Service Manual Int l 19 ...
Page 23: ...Low Profile 1600 Series Advantage Digital Service Manual Int l 23 ...
Page 25: ...Low Profile 1600 Series Advantage Digital Service Manual Int l 25 ...
Page 27: ...Low Profile 1600 Series Advantage Digital Service Manual Int l 27 ...
Page 29: ...Low Profile 1600 Series Advantage Digital Service Manual Int l 29 ...
Page 32: ...Low Profile 1600 Series Advantage Digital Service Manual Int l 32 ...