background image

13

/15

Comply with the minimum distances indicated on section Minimum 

distances 

 

†

Single fire damper wall opening

A rectangular opening must be provided in the wall with a frame 

made by metal profiles ideal for use with plasterboard (min. thick-

ness 0,6 mm) with a side 75 mm greater than the nominal size of 

the damper. It is advisable not to exceed by more than 10 mm from 

the indicated sizes so as not to compromise the correct  thermal in-

sulation.

The perimeter of the opening must be covered with a layer of plas-

terboard as wide as the thickness of the wall. 

 

†

Paired fire dampers wall opening

A rectangular opening must be provided in the wall with a frame 

made by metal profiles ideal for use with plasterboard (min. thick-

ness 0,6 mm) with a side 75 mm greater than the nominal size of the 

paired dampers:

– Vertically paired fire dampers

base = damper base + 75 mm

height = h h 45 mm + 75 mm

– Side by side paired fire dampers

base = base1 + base2 + 45 mm + 75 mm

height = damper 75 mm.

The perimeter of the opening must be covered with a layer of plas-

terboard as wide as the thickness of the wall. 

It is advisable not to exceed by more than 10 mm from the indicated 

sizes so as not to compromise the correct thermal insulation.

B.  Nominal base dimension (mm)

H.  Nominal height dimension (mm)

1.  Rock wool, 100 kg/m³

2.  Plasterboard infill panel, thickness 12,5 mm

3.  Plasterboard thickness 12,5 mm

 

†

Damper positioning

Lift the fixing flaps located on the fire damper casing. See section 

Fixing flaps  for further details.

Position the damper in the opening so that the side of the closing 

mechanism extends from the wall by 185 mm.

Be careful not to damage the intumescent gasket on the outside the 

casing.

Secure the fire damper to the wall using four screws on the four holes 

of the fixing flaps.

The double test (with the mechanism inside and outside the fire 

area) demonstrated that there is no preferred direction for the po-

sition of the damper, both in relation to air flow and the side with 

the higher probability of exposure to fire, as indicated in standard 

EN1366-2 (paragraph 6.2).

 

†

Filling

It is not necessary to insert any material, but simply cover the gap 

between the damper and the wall by applying on face of the wall 

mechanism side a layer of plasterboard, to a total minimum thickness 

of 12,5 mm, to make a frame 100 mm wide.

1.  Plasterboard infill panel, thickness 12,5 mm

2.  Plasterboard infill panel, thickness 12,5 mm

3.  Rock wool density up to 100 kg/m³ (optional)

4.  Plasterboard thickness 12,5 mm

5.  Self-drilling screw Ø 3,5 X 45 mm

 

„

EI 120 S Installation within vertical light wall (plasterboard) - 

Special cases

 

†

Installation in contact with ceiling or floor or side wall

A rectangular opening must be provided in the wall with the three 

sides made by metal profles ideal for use with plasterboard. The side 

parallel to the ceiling or to the wall 75 mm greater than the nominal 

sizes of the damper and the side perpendicular to the ceiling or to 

the floor 63 mm greater than the nominal sizes of the damper.

The three metal profiles must be covered with a plasterboard layer 

12,5 mm thick, as wide as the the thickness of the wall.

No need to apply anything on the wall or on the ceiling.

Just apply three plasterboard layers, to compose a “U” shape on the 

three free sides of the fre damper.

This installation is allowed for two fire dampers paired in battery as 

well.

 

†

Corner room installation

A rectangular opening must be provided in the wall with the two 

sides made by metal profles ideal for use with plasterboard. The 

opening size must be 63 mm greater than the nominal sizes of the 

damper.

The two metal profiles must be covered with a plasterboard layer 

12,5 mm thick, as wide as the the thickness of the wall.

No need to apply anything on the wall or on the ceiling.

Apply two plasterboard layers, to compose a “L” shape on the two 

free sides of the fre damper.

This installation is allowed for two fire dampers paired in battery as 

well.

In case of two side by side paired fre dampers it is necessary to 

position the fre dampers with vertical axis, due to the mechanism 

presence.

Summary of Contents for EI 120 S

Page 1: ...l data the equipment and acces sories indicated could be subject to variations Installation booklet RECTANGULAR SERIES WKS25 500 Pa Cert N 1812 CPR 1046 EN 15650 This is a 15 page installation booklet...

Page 2: ...sity 995 kg m Plasterboard sealing ve i o D B x H min 100 x 200 max 800 x 600 B x H min 100 x 200 max 800 x 600 B x H min 100 x 200 max 800 x 600 EI 120 S Installation within vertical light wall gypsu...

Page 3: ...l axis Fixing flaps 1 Bend for walls 100 mm thick or higher 2 Bend for walls 70 mm thick or higher Fire dampers pairing The patented WKS25 rectangular fire dampers can be paired side by side or vertic...

Page 4: ...atically closes the blade when the temperature in the duct exceeds 70 C or 95 C for the fire damper with 95 C thermal fuse It is possible to close the damper by pressing the indicated button Blade ope...

Page 5: ...perature sensor or cut off the power supply Blade opening mode The damper must be opened when the ventilation system if switched off To open the damper with the electric motor driven actuator provide...

Page 6: ...Normally open C Common NF Normally closed Manual with magnet MR MI version the magnet is powered using 24 V DC 48 V DC through S0 25 electric board S0 25 electronic board S2 optional for 24V DC 48V DC...

Page 7: ...4V AC DC WKS25VSS Siemens GRA126 Opening 3 5 W In stand by 2 W Motor 230V AC WKS25VSS Siemens GRA326 Opening 4 5 W In stand by 3 5 W Microswitches position contacts Manual control version 12VDC 2A 125...

Page 8: ...itioning The fire damper can be installed both with the blade axis positioned vertically or horizontally Positioning brackets before fixing 1 Positioning brackets Installation of flexible connectors i...

Page 9: ...L1 L2 200 50 50 250 50 100 300 50 100 350 50 150 400 50 150 450 50 200 500 50 200 550 50 250 600 100 250 H Nominal height of fire damper L1 End cap length mechanism side L2 End cap length mechanism o...

Page 10: ...l floor used for the test and wall floor used for the actual installation The test results obtained on a type of wall floor are valid also for walls floor of the same type but with greater thickness a...

Page 11: ...tach to the steel pro file underneath 1 Plasterboard thickness 12 5 mm 2 Rock wool density up to 100 kg m optional 3 Horizontal U shaped profile 4 Vertical C shaped profile 5 Self drilling screw 3 5 X...

Page 12: ...located on the fire damper casing See section Fixing flaps for further details Position the damper in the opening so that the side of the closing mechanism extends from the wall by 185 mm Be careful n...

Page 13: ...r both in relation to air flow and the side with the higher probability of exposure to fire as indicated in standard EN1366 2 paragraph 6 2 Filling It is not necessary to insert any material but simpl...

Page 14: ...5 mm 2 Self drilling screw 3 5 X 45 mm EI 120 S Installation within vertical light wall gypsum blocks wall The WKS25 fire dampers classified EI 120 S within vertical light walls built with gypsum bloc...

Page 15: ...al wall Installation within vertical light wall Shaft wall WKS25 fire dampers are tested and approved in Fire resistance classification Hole size D1 x D2 mm Damper protrusion from the wall E mm Wall m...

Reviews: