9
/15
Components (Transfer Application)
1. Extension duct with net, 12 x 12 mm mesh opening
2. Fire damper
3. M8 nut
4. M8 screw
Technical data (Transfer Application)
1. Mechanism side
2. Mechanism opposite side
3. End cap with mesh
L1 End cap length mechanism side
L2 End cap length mechanism
opposite side
H Nominal height of fire damper
Length of end cap with mesh depending on fire damper
height H.
H
L1
L2
200
50
50
250
50
100
300
50
100
350
50
150
400
50
150
450
50
200
500
50
200
550
50
250
600
100
250
H
Nominal height of fire damper
L1
End cap length mechanism side
L2
End cap length mechanism opposite side
Minimum distances
It is recommended to keep enough space for using the control
mechanism or for maintenance.
In accordance with Articles 7 and 13 of EN 1366-2 respect the mini-
mum distances indicated below.
Minimum distances
1. Side vertical wall
2. Floor
a. Distance between fire dampers installed within vertical wall
b. Distance between fire damper and vertical lateral wall / floor