ovER vIEw
FBC
1 - 4 - 7
5
/34
rev 20-02
Fire resistance classification according to EN 13501-3-2009
EI 120 S
(300 Pa)
EI 90 S
(300 Pa)
EI 60 S
(300 Pa)
EI 30 S
(300 Pa)
Rigid w
all
Installations within vertical rigid wall
Wall minimum thickness 100 mm
Wall minimum density 550 kg/m³
Mortar or plaster putty sealing
ve (i
↔
o)
W
FBC7
FBC7
FBC4
FBC7
FBC4
FBC1
FBC7
FBC4
FBC1
Installations within vertical rigid wall
Wall minimum thickness 100 mm
Wall minimum density 550 kg/m³
Plasterboard and rock wool 40 kg/m³ or mortar or plaster putty
sealing
ve (i
↔
o)
D/W
FBC7
FBC7
FBC4
FBC7
FBC4
FBC1
FBC7
FBC4
FBC1
Fle
xible w
all
Installations within vertical light wall (plasterboard)
Wall minimum thickness 100 mm
Wall rock wool density according to fire resistance class of the wall
Plasterboard and rock wool kg/m³ or mortar or plaster putty
ve (i
↔
o)
D/W
FBC7
FBC7
FBC4
FBC7
FBC4
FBC1
FBC7
FBC4
FBC1
Installations within vertical light wall (plasterboard)
Wall minimum thickness 100 mm
Wall rock wool density according to the fire resistance class of the
wall
Mortar or plaster putty sealing
ve (i
↔
o)
W
FBC1
FBC1
Floor
Installations within floor
Floor minimum thickness 150 mm
Floor minimum density 550 kg/m³
Mortar sealing
ho (i
↔
o)
W
FBC7
FBC7
FBC4
FBC7
FBC4
FBC1
FBC7
FBC4
FBC1
Floor minimum thickness 100 mm
Floor minimum density 550 kg/m³
Mortar sealing
ho (i
↔
o)
W
-
FBC7
FBC4
FBC7
FBC4
FBC1
FBC7
FBC4
FBC1
W
Wet method sealing
D
Dry method sealing
ve
Vertical installation
ho
Horizontal installation
(i
↔
o) Origin of fire irrelevant
Pa
Pascal of depression
E Integrity
I
Thermal insulation
S
Smoke seal
Cert. N° FBC1 1812-CPR-1630,FBC4 1812-CPR-1632,FBC7 1812-CPR-1634
Fire Batt (Weichschott) sealings
EI 120 S
(300 Pa)
EI 90 S
(300 Pa)
EI 60 S
(300 Pa)
EI 30 S
(300 Pa)
Rigid w
all
Installations within vertical wall with Fire Batt (Weichschott) sealing
Wall minimum thickness 100 mm
Wall minimum density 550 kg/m³
Rock wool 140 kg/m³ and endothermic varnish sealing
ve (i
↔
o)
W
FBC7
FBC7
FBC4
FBC7
FBC4
FBC1
FBC7
FBC4
FBC1
Fle
xible w
all
Installations within vertical wall with Fire Batt (Weichschott) sealing
Wall minimum thickness 100 mm
Wall rock wool density according to fire resistance class of the wall
Rock wool 140 kg/m³ and endothermic varnish sealing
ve (i
↔
o)
W
FBC7
FBC7
FBC4
FBC7
FBC4
FBC1
FBC7
FBC4
FBC1
FBC
1 - 4 - 7
5