2
/14
OVER VIEW
Fire resistance classification according to EN 13501-3-2009
Rigid wall
EI 60 S
(300 Pa)
EI 30 S
(300 Pa)
EI 60S Installation within vertical rigid wall hole Ø+30
Wall minimum thickness 95 mm
Wall minimum resistance class EI 60
Mortar or plaster putty or rock wool 35 kg/m³ density sealing
ve (i
↔
o)
D/W
Ø
min 100
max 400
Ø
min 100
max 400
EI 60S Installation within vertical rigid wall hole Ø+10
Wall minimum thickness 95 mm
Minimum resistance class EI 60
Acrilic sealant sealing
ve (i
↔
o)
D
Ø
min 100
max 400
Ø
min 100
max 400
Flexible wall
EI 60 S
(300 Pa)
EI 30 S
(300 Pa)
Installations within vertical light wall EI 60 S hole Ø+30
Wall minimum thickness 95 mm
Wall rock wool density up to 35 kg/m³ (optional)
Studs made of steel or timber
mortar or plaster putty or rock wool 35 kg/m³ and acrilic sealant sealing
ve (i
↔
o)
D/W
Ø
min 100
max 400
Ø
min 100
max 400
Installations within vertical light wall EI 60 S hole Ø+10
Wall minimum thickness 95 mm
Wall rock wool density up tp 35 kg/m³ (optional)
Studs made of steel or timber
Acrilic sealant sealing
ve (i
↔
o)
D
Ø
min 100
max 400
Ø
min 100
max 400
Floor
EI 60 S
(300 Pa)
EI 30 S
(300 Pa)
Installation within floor
Floor minimum thickness 100 mm
Floor minimum density 550 kg/m³
Mortar or plaster putty or rock wool 35 kg/m³ sealing
ho (i
↔
o)
D/W
Ø
min 100
max 400
Ø
min 100
max 400
Ø is the minimum and maximum nominal diameter of fire dampers in mm
ve
Vertical installation
ho
Horizontal installation
(i
↔
o) Origin of fire irrelevant
Pa
Pascal of depression
E Integrity
I
Thermal insulation
S
Smoke seal
W
Wet method sealing
D
Dry method sealing
Cert. N° 1812-CPR-1639
Installation remote from construction support
Rigid wall
EI 60 S
(300 Pa)
EI 30 S
(300 Pa)
EI 60 S Installation remote from the vertical rigid wall hole Ø+30
Wall minimum thickness 95 mm
Wall minimum resistance class EI 60
Mortar or plaster putty or rock wool 35 kg/m³ density sealing
ve (i
↔
o)
D/W
Ø
min 100
max 400
Ø
min 100
max 400
EI 60S Installation remote from the vertical rigid wall hole Ø+10
Wall minimum thickness 95 mm
Minimum resistance class EI 60
Acrilic sealant sealing
ve (i
↔
o)
D
Ø
min 100
max 400
Ø
min 100
max 400
rev 20-12
2
We reserve the right to make changes without prior notice