background image

5

/14

Electrical wiring for Belimo BFL24-SR-T modulating motorized version

24V AC/DC power supply

 /-  Negative (DC) or neutral (AC) black wire

~/+ Positive (DC) or phase (AC) red wire

3  Positioning signal Y

5  Positioning feedback U (max 0,5mA)

Microswitches position contacts

S1  Common closed damper microswitch

S2  Normally closed, closed damper microswitch

S3  Normally opened, closed damper microswitch

S4  Common open damper microswitch

S5  Normally closed, open damper microswitch

S6  Normally opened, open damper microswitch

Tf  Thermal fuse

TECHNICAL DATA

The sizes shown are in mm.

 

„

Dimension

Ø

mm

100

125

160

200

250

315

400

S blade 

exposition

mm

0

0

0

30

40

80

157

Lp

mm

40

40

40

40

60

60

80

Lp 

Overlap length between fire damper and duct

MAINTENANCE AND 

INSPEC TIONS

Fire dampers and control mechanisms do not require routine main-

tenance.

Extraordinary maintenance (repairs) and periodic inspection opera-

tions are the responsibility of the ventilation system operator.

It is recommended to keep enough space (about 200mm) for using 

or replacing the control mechanism or for maintenance. Also provide 

the necessary space to remove the ventilation duct from the damper 

whenever necessary.

It is recommended to provide inspection hatches on both sides of 

the ducts connected to the fire damper.   

The implementation of a periodic inspection plan allows to guaran-

tee the efficiency and functionality of the fire dampers for the fire 

safety of the building.

 

„

Periodic inspection and cleaning

Periodic inspection shall be performed in accordance with the re-

quirements of the law or by the building regulations or other local 

regulations.

In the absence of specific regulations (or to their complement), in ac-

cordance with point 8.3 of the EN 1560 standard, it is recommended 

to carry out the following control activities at intervals of no more 

than 12 months:

•  Check the servomotor electrical wiring for damage (where appli-

cable);

•  Check end-switch wiring for damage (where applicable);

•  Check damper cleanliness and clean where necessary;

•  Check the condition of blades and seals, rectify and report where 

necessary;

•  Check the correct opening and closing of the fire damper by ma-

nual operation according to the instructions in the technical ma-

nual of the fire damper;

•  Check the opening and closing operation of the damper control-

led by the fire alarm system (if present);

•  Check the operation of the end switches in open and closed state, 

adjust and report if necessary;

•  Confirm that the damper fulfils its function as part of the control 

system (where necessary);

•  Check that the damper is left in its normal operating position, whi-

ch usually corresponds to the open position.

 

„

Repair

For safety reasons, repair activities involving fire-fighting componen-

ts must be carried out only by qualified personnel.

Only original spare parts supplied by the fire damper manufacturer 

must be used.

A functional test must be performed after each repair.

.

At the end of the inspection, cleaning or repair operations, check that 

the fire damper is in the normal operating position.

Keep records of all inspections, repair activities, any problems en-

countered and their resolution.

This practice, even when not mandatory, is very useful in practice.

 

„

Disposal

Disposal in case of destruction must be carried out in accordance 

with national legislation. For electrical and electronic parts also refer 

to EU Directive 2011/65.

INSTALLATION

The sizes shown are in mm.

It is recommended to perform a functional test before Installation to 

exclude possible damage during transport and another test imme-

diately after installation to exclude accidental damage to the product 

and interference with mounting components.

 

„

Blade rotation axis positioning

The fire damper can be installed with the blade axis positioned verti-

cally or horizontally or tilted at any angle.

rev 20-12

5

We reserve the right to make changes without prior notice

Summary of Contents for FNC1

Page 1: ...p3 italia it 1MUBFNC1EN rev 20 12 1MUBFNC1EN FNC1 FNC1 l indab we simplify co nstruc tio n www lindab com Fire dampers are manufactured by MP3 Srl www mp3 italia it 1MUBFNC1EN LIND rev 20 12 1MUBFNC1E...

Page 2: ...tuds made of steel or timber Acrilic sealant sealing ve i o D min 100 max 400 min 100 max 400 Floor EI 60 S 300 Pa EI 30 S 300 Pa Installation within floor Floor minimum thickness 100 mm Floor minimum...

Page 3: ...2 C or 95 C for the 95 C version To close the damper when the motor is connected press the switch on the temperature sensor or cut off the power supply Blade opening mode Make sure that the damper is...

Page 4: ...uest ELECTRICAL CONNECTIONS Electrical wiring Electrical connections must be done by qualified and trained people Switch off the power supply before starting any work on the electric elements Never sw...

Page 5: ...Check the servomotor electrical wiring for damage where appli cable Check end switch wiring for damage where applicable Check damper cleanliness and clean where necessary Check the condition of blades...

Page 6: ...The test results obtained on a type of wall floor are valid also for wal ls floor of the same type but with greater thickness and or density than those used in the test For plasterboard walls the tes...

Page 7: ...be provided in the wall as indicated in the table and in the drawing Damper positioning Position the damper in the opening so that the side of the closing mechanism extends as indicated in the drawing...

Page 8: ...Firecryl or equivalent with resistance and reaction to fire equal or higher to cover the sealing D Hole size see table above Installations within vertical rigid wall EI 60 S hole 10 1 Positioning brac...

Page 9: ...ion duct 5 Rock wool 35 kg m or mortar or plaster putty 6 Fire stopping sealant reference Soudal Firecryl or equivalent with resistance and reaction to fire equal or higher between refractory ring and...

Page 10: ...in the drawing For distance between fire damper and wall less than or equal to 1m only one support is enough as indicated in the drawing The support at 20 mm from the fire damper is always mandatory...

Page 11: ...her to cover the sealing D Hole size see table above a 1000mm MAX n of threaded rods depending on the length of the duct use 1 threaded bar for a 1000 mm EI 60 S Installation remote from the vertical...

Page 12: ...ed in the drawing Fire resistance classification D hole size mm Wall minimum thickness S mm Sealing EI 60 S Installation remote from the vertical light wall Wall resistance class EI 60 EI 60 S 300 Pa...

Page 13: ...fire equal or higher between insulation and construction support 8 Self drilling screw 4 2 X 13 mm x4 9 Insulation rock wool Pro Wired Mat 80 AL 1 Paroc or equivalent see Installation remote from ver...

Page 14: ...ess 70 mm or equi valent A metallic mesh is installed around the rock wool The junctions between the insulation and the damper are made by an acrylic fire stopping sealant es Soudal Firecryl or equiva...

Reviews: