15
Fire resistance classification
Hole size “D1 x D2”
[mm]
Damper protrusion from
the wall “E”
[mm]
Wall minimum thickness “S”
[mm]
Sealing
EI 120 S Installation within vertical light wall (plasterboard)
Wall rock wool minimum density 100
kg/m³
EI 120 S
(500 Pa)
From (B+75) x (H+75)
to (B+95) x (H+95)
185
100
Rock wool 100 kg/m³
with infill plasterboard
(thickness 12.5 mm)
B
Nominal base of the damper
H
Nominal height of the damper
D1 Hole base: see table above
D2 Hole height: see table above
E Damper protrusion from the wall: see table above
1. Plasterboard infill panel, thickness 12,5 mm
2. Plasterboard infill panel, thickness 12,5 mm
3. Rock wool, 100 kg/m³
4. Plasterboard thickness 12,5 mm
5. Self-drilling screw Ø 3,5 X 45 mm
6. Metal frame
Installations within vertical light wall (gypsum blocks wall)
Refer to the section Construction supports characteristics for further
information.
Comply with the minimum distances indicated on section Minimum
distances .
Wall opening
A opening must be provided in the wall as indicated in the table and
in the drawing
In case of paired installation refer to the section Fire dampers pairing
for further information
Damper positioning
Position the damper in the opening so that the side of the closing
mechanism extends as indicated in the table and in the drawing.
Filling
It is not necessary to insert any material, but simply cover the gap
between the damper and the wall by applying on both faces of the
wall a layer of plasterboard, to a total minimum thickness of 12,5 mm
per side, to make a frame 100 mm wide.
Fire resistance classification
Hole size “D1 x D2”
[mm]
Damper protrusion from
the wall “E”
[mm]
Wall minimum thickness “S”
[mm]
Sealing
EI 90 S Installation within vertical light wall (gypsum blocks wall)
(paired installation not available)
Wall minimum density 995 kg/m³
EI 90 S
(500 Pa)
From (B+50) x (H+50)
to (B+70) x (H+70)
202
70
Plasterboard sealing
EI 120 S Installation within vertical light wall (gypsum blocks wall)
Wall minimum density 995 kg/m³
EI 120 S
(500 Pa)
From (B+50) x (H+50)
to (B+70) x (H+70)
185
100
Plasterboard sealing
B
Nominal base of the damper
H
Nominal height of the damper