11
Communication and control devices
BKSE 24-6
Power voltage
AC 24V 50/60Hz
Power consumption
3,5W (operating position)
Dimensioning
5,5VA 18 A (Imax6.4 A @ 2.5ms)
Protection class
III (low voltage)
Degree of protection
IP 20
Ambient operation temperature
0 …+50°C
Connection
screw terminals for 2x1.5mm
2
conductor
lindab | we simplify construction
Smoke Control Damper
SDJR-S
Lindab reserves the right to make changes without prior notice
Last modified: 2021-09-03
Rev: 2021-03-26
Fig. 12
Communication and control devices BKSE 24-6
Tab. 2.4.1. Communication and control devices BKSE 24-6
2.4. Communication and control device
BKSE 24-6 indicates operating condition and faults of flue dampers. These conditions can be signalled or transmitted to the
higher-level control system via the auxiliary built-in contacts. Signals from individual BKNE 230-24 are evaluated separately.
All BKNE 230-24 are controlled simultaneously. A maximum of 6 BKNE 230-24 can be connected to the BKSE 24-6.
Damper control is ensured with a simple 2-wire line. The damper's correct function is indicated by two LEDs. The operating
status of the entire control system and any errors are indicated by these LEDs and the corresponding error LED.
Mounting and connection of BKSE 24-6 can be done on a 35mm DIN rail. It's connected using two 9-pin terminal blocks
(plug connectors).