TECHNICAL DATA

 

„

Dimension

Ø

mm

100

125

140

150

160

180

S blade exposition

mm

0

0

0

0

0

0

Lp

mm

38

38

38

38

38

38

Ø

mm

200

224

250

280

300

315

S blade exposition

mm

0

1

0

10

20

28

Lp

mm

38

38

57

57

57

57

Lp 

Overlap length between fire damper and duct

MAINTENANCE AND INSPEC TIONS

Fire dampers and control mechanisms do not require routine main-

tenance.

Extraordinary maintenance (repairs) and periodic inspection opera-

tions are the responsibility of the ventilation system operator.

The implementation of a periodic inspection plan allows to guaran-

tee the efficiency and functionality of the fire dampers for the fire 

safety of the building.

 

„

Periodic inspection and cleaning

Periodic inspection shall be performed in accordance with the re-

quirements of the law or by the building regulations or other local 

regulations.

In the absence of specific regulations (or to their complement), in ac-

cordance with point 8.3 of the EN 1560 standard, it is recommended 

to carry out the following control activities at intervals of no more 

than 6 months:

•  If the damper is connected to a remote control or command sys-

tem (eg BMS or alarm or fire detection), that responds correctly to 

commands by performing at least one opening and closing test 

and verifying the correct movement of the blade and the correct 

functioning of the microswitches (limit switches).

•  If the damper is not connected to a remote control or command 

system, manually execute an opening and closing test and check 

the correct movement of the blade and the correct functioning of 

the microswitches (limit switches) if present.

Together with the control activities, it is recommended to visually 

verify the absence of corrosion, the integrity of the electrical wiring 

and the sealing of the construction support.

Damper cleaning is included in the ordinary maintenance activities 

of the ventilation ducts.

Fire dampers can be cleaned with a dry or wet cloth.

In the case of resistant dirt, it is possible to use normal household 

detergents.

If prescribed for the type of building, it is possible to use disinfectant 

detergents.

The use of detergents or mechanical abrasive cleaning systems is not 

permitted.

These indications comply with the standards EN 15650 annex D and 

EN 15423 annex C.

 

„

Repair

For safety reasons, repair activities involving fire-fighting compo-

nents must be carried out only by qualified personnel.

Only original spare parts supplied by the fire damper manufacturer 

must be used.

A functional test must be performed after each repair.

.

At the end of the inspection, cleaning or repair operations, check that 

the fire damper is in the normal operating position.

Keep records of all inspections, repair activities, any problems en-

countered and their resolution.

This practice, even when not mandatory, is very useful in practice.

 

„

Disposal

Disposal in case of destruction must be carried out in accordance 

with national legislation. For electrical and electronic parts also refer 

to EU Directive 2011/65.

INSTALLATION

The sizes shown are in mm.

Summary of Contents for WH25

Page 1: ...esthetic or dimensional features the technical data the equipment and acces sories indicated could be subject to variations Cert N 1812 CPR 1023 EN 15650 This is a 23 page installation booklet www mp3...

Page 2: ...opening lever 2 Manual closing button 3 Lever position when the blade is open 4 Lever position when the blade is closed Blade closing mode Automatic closing with thermal fuse The control mechanism has...

Page 3: ...tion of thermosensitive element for auto matic damper closing 72 C 7 C Standard 95 C 9 C On request Siemens motorized version 1 Manual closing switch 2 Manual opening lever 3 Screwdriver 4 Position in...

Page 4: ...al light wall plasterboard Wall minimum thickness 100 mm Wall rock wool density up to 80 kg m optional Mortar or plaster putty sealing ve i o W min 100 max 315 min 100 max 315 min 100 max 315 min 100...

Page 5: ...y 140 kg m and endothermic varnish sealing ve i o W min 100 max 315 min 100 max 315 min 100 max 315 min 100 max 315 Minimum distance allowed between 2 dampers 200 mm 50 mm 50 mm 50 mm EI 120 S Install...

Page 6: ...from the vertical light wall gypsum blocks wall Wall minimum thickness 100 mm Wall minimum density 995 kg m Mortar or plaster putty sealing ve i o W min 100 max 315 min 100 max 315 min 100 max 315 min...

Page 7: ...microswitches included 1 Microswitch contacts for blade position 2 Magnet power supply contacts 24V DC or 48V DC Keep to the polarity for input magnet MAG Magnet power supply FCU Closed blade contact...

Page 8: ...oswitch S6 Normally opened open damper microswitch Electrical specifications Manual and compact manual Manual with magnet Belimo motorized version Siemens motorized version Voltage and power consumpti...

Page 9: ...command system manually execute an opening and closing test and check the correct movement of the blade and the correct functioning of the microswitches limit switches if present Together with the con...

Page 10: ...in case of fire It is recommended not to compress flexible connectors in the in stallation phase Flexible connector must be at least 100mm long and in order that possible duct thermal expansions are b...

Page 11: ...n within vertical rigid wall Plasterboard and rock wool 100 kg m sealing 50 75 Flexible wall EI 120 S Installation within vertical light wall plasterboard Mortar or plaster putty sealing 50 75 EI 90 S...

Page 12: ...aling Rock wool 140 kg m and endothermic varnish sealing 200 110 Floor EI 120 S Installation remote from the floor Mortar or plaster putty sealing 200 110 EI 90 S Installation remote from the floor Mo...

Page 13: ...unalinged to avoid alignment between the joints of the layer above and below the front plasterboards layers are fixed using long enough screws to pass through the lower plasterboard and attach to the...

Page 14: ...ith pre formed slabs with interlocking shaped edges according to the fol lowing characteristics minimum thickness 100 or 150 mm according to the resistance class required minimum density 2200 kg m Ins...

Page 15: ...en the wall and the damper as indicated in the table and in the drawing Fire resistance classification D hole size mm Wall minimum thickness S mm Sealing EI 60 S Installation within vertical light wal...

Page 16: ...995 kg m EI 90 S 500 Pa From 25 to 35 circular hole 100 Plaster putty sealing 1 Plaster putty D Hole size see table above S Wall minimum thickness see table above Lp Overlap length between fire dampe...

Page 17: ...h an internal perimeter sealant type PROMASTOP E PASTE or HILTI CFS S ACR minimum thickness of 1 mm Fire resistance classification D hole size mm Wall minimum thickness S mm Sealing Rigid wall EI 120...

Page 18: ...rigid wall and the vertical light wall gypsum blocks wall Refer to the section Construction supports characteristics for further information Comply with the minimum distances indicated on section Mini...

Page 19: ...he table and in the drawing Damper positioning Connect fire damper to the galvanized steel duct as indicated in the drawing with 4 screws 4 2x13 Install the damper with the mechanism facing away from...

Page 20: ...ck wool sealing 14 Rock wool density up to 80 kg m optional 15 Metal frame Installations remote from the vertical wall with Fire Batt Weichschott sealing Refer to the section Construction supports cha...

Page 21: ...panel 50 mm thick with 140 kg m density 2 PROMASTOP E PASTE or HILTI CFS S ACR type sealant 3 PROMASTOP E PASTE or HILTI CFS CT endothermic varnish 4 Wall indicated in the table above 5 Self drilling...

Page 22: ...13 mm 2 PROMASTOP E PASTE or HILTI CFS S ACR type sealant 3 PROMASTOP E PASTE or HILTI CFS CT endothermic varnish 4 Screws M8 x 40 mm 5 Washers 15 x 9 mm 6 Angle connector 105 X 105 X 90 mm 7 Washers...

Page 23: ...From 50 x 50 To 70 x 70 square hole 90 Mortar or plaster putty with infill plasterboard thickness 20 mm 1 Plasterboard thickness 20 mm 2 Plasterboard arch infill thickness 20 mm 3 Mortar M 10 EN998 2...

Reviews: