background image

14

/17

EI 90 S Installation within vertical light wall (plasterboard)

D1  Hole base: see table above

D2  Hole height: see table above

E  Damper protrusion from the wall: see table above

1.  Plasterboard infill panel, thickness 12,5 mm

2.  Plasterboard infill panel, thickness 12,5 mm

3.  Rock wool, 100 kg/m³

4.  WKGY100 fixing brackets (accessory to order separately, one size valid for all 

fire dampers kind  and wall thickness)

5.  Rock wool density up to 100 kg/m³ (optional)

6.  Plasterboard thickness 12,5 mm

7.  Self-drilling screw Ø 3,5 X 45 mm

8.  Metal frame

EI 120 S Installation within vertical light wall (plasterboard)

D1  Hole base: see table above

D2  Hole height: see table above

E  Damper protrusion from the wall: see table above

1.  Mortar M-10, EN998-2 or plaster

2.  Rock wool density up to 100 kg/m³ (optional)

3.  Plasterboard thickness 12,5 mm

4.  Metal frame

 

„

Installations within vertical light wall (gypsum blocks wall)

Refer to the section  for further information.

Comply with the minimum distances indicated on section Minimum 

distances 

 

†

Wall opening

A opening must be provided in the wall as indicated in the table and 

in the drawing

 

†

Damper positioning

Position the damper in the opening so that the side of the closing 

mechanism extends as indicated in the table and in the drawing.

 

†

Filling

Fill the space between the wall and the damper as indicated in the 

table and in the drawing.

Fire resistance classification 

Hole size “D1 x D2”

[mm]

Damper protrusion from 

the wall “E”

[mm]

Wall minimum thickness “S”

[mm]

Sealing

EI 90 S Installation within vertical light wall (gypsum blocks wall) 

(paired installation not available)

Wall minimum density 995 kg/m³

EI 90 S

(500 Pa)

From (B+80) x (H+80)

to (B+110) x (H+110)

220

70

Plaster putty sealing

EI 120 S Installation within vertical light wall (gypsum blocks wall)

Wall minimum density 995 kg/m³

EI 120 S

(500 Pa)

From (B+80) x (H+80)

to (B+110) x (H+110)

205

100

Plaster putty sealing

Nominal base of the damper

Nominal height of the damper

1.  Plaster putty

D1  Hole base: see table above

D2  Hole height: see table above

E  Damper protrusion from the wall: see table above

S  Wall minimum thickness: see table above 

 

„

Installations within floor

Refer to the section Construction supports characteristics  for further 

information.

Comply with the minimum distances indicated on section Minimum 

distances 

Summary of Contents for WK45 Series

Page 1: ...data the equipment and acces sories indicated could be subject to variations Installation booklet RECTANGULAR SERIES WK45 500 Pa 300 Pa Cert N 1812 CPR 1006 EN 15650 This is a 17 page installation bo...

Page 2: ...ling ve i o D B X H min 200 X 200 max 1500 X 800 B X H min 200 X 200 max 1500 X 800 B X H min 200 X 200 max 1500 X 800 EI 120 S Installation within vertical light wall gypsum blocks wall Wall minimum...

Page 3: ...sealing Wall minimum thickness 100 mm Wall minimum density 995 kg m Rock wool 140 kg m and endothermic varnish sealing ve i o W B X H min 200 X 200 max 1500 X 800 B X H min 200 X 200 max 1500 X 800 B...

Page 4: ...r In case of closed damper as a result of the action of the thermosen sitive element it is possible to manually reopen the damper by rotat ing the lever counterclockwise once the element has been repl...

Page 5: ...sing by remote control If power to the motor is cut off the blade will close Temperature calibration of thermosensitive element for auto matic damper closing 72 C 7 C Standard 95 C 9 C On request Fire...

Page 6: ...roswitch When the fire blade is closed the circuit is closed 3 NC contact of SA microswitch When the fire blade is open the circuit is open 4 NO contact of SA microswitch When the fire blade is open t...

Page 7: ...24V DC or 230 V AC version Motor 24V AC DC WK45VMB Belimo BFN24T Opening 4 W In stand by 1 4 W Motor 230V AC WK45DMB Belimo BFN230T Opening 5 W In stand by 2 1 W Motor 24V AC DC WK45VGB Belimo BF24T O...

Page 8: ...volving fire fighting compo nents must be carried out only by qualified personnel Only original spare parts supplied by the fire damper manufacturer must be used A functional test must be performed af...

Page 9: ...ntion fire resistance classification for transfer application is conform to section Fire resistance classification according to EN 13501 3 2009 limited to EI 120S if the ducted classification is high...

Page 10: ...k wool 100 kg m sealing 70 75 Yes One air duct Flexible wall EI 120 S Installation within vertical light wall plasterboard Mortar or plaster putty sealing 70 75 Yes Separate air duct EI 90 S Installat...

Page 11: ...ls floor of the same type but with greater thickness and or densi ty than those used in the test For plasterboard walls the test results are also valid for walls with a greater number of plasterboard...

Page 12: ...haped edges as indicated in the supplier s instruc tions and according to the following characteristics minimum thickness 70 or 100 mm according to the type and re sistance class required minimum dens...

Page 13: ...bove D2 Hole height see table above E Damper protrusion from the wall see table above Installations within vertical light wall plasterboard Refer to the section Construction supports characteristics f...

Page 14: ...provided in the wall as indicated in the table and in the drawing Damper positioning Position the damper in the opening so that the side of the closing mechanism extends as indicated in the table and...