Flexible connector must be normal flammability and in case of fire 

the grounding bonding should disconnet to guarantee the com-

plete separation between fire damper and connected air duct.

When flexible connectors made of conductive material (e.g. alumi-

num) are used, no additional grounding bonding is required.

Despite flexible connector installation, the fire damper must be in-

stalled in the construction support so that its weight does not affect 

damper’s installation position both during normal operation and in 

case of fire.

It is recommended not to compress flexible connectors in the in-

stallation phase.

Flexible connector must be at least 100mm long and in order that 

possible duct thermal expansions are balanced. 

Take care that the flexible connector does not interfer with opening 

/ closing movement of the blade.

 

„

Transfer Application (application not connected to air ducts on 

one or both sides)

Following tests performed as per EN 1366-2, section 6.3.6 Standard, 

it is possible to install the fire damper free from air duct from one or 

both sides.

•  Attention: fire resistance classification for transfer application is 

conform to section Fire resistance classification according to EN 

13501-3-2009  limited to EI 120S if the ducted classification is high-

er.

•  End cap with mesh shall be mounted on the side not connected 

to air duct.

•  End cap with mesh is made from galvanized steel sheet and in-

cludes nuts and screws for fixing on fire damper.

•  End cap with mesh is supplied loose from the fire damper.

 

†

Components (Transfer Application)

1.  End cap with mesh

2.  Fire damper

3.  M10 nut

4.  M10 screw

 

†

Technical data (Transfer Application)

1.  Mechanism side

2.  Mechanism opposite side

3.  End cap with mesh

L1  End cap length mechanism side

L2  End cap length mechanism 

opposite side

H  Nominal height of fire damper

Length of end cap with mesh depending on fire damper 

height H.

H

L1

L2

200

50

50

250

50

50

300

50

50

350

50

50

400

50

50

450

50

50

500

50

50

550

50

50

600

50

50

650

100

100

700

100

100

750

150

150

800

150

150

Nominal height of fire damper

L1 

End cap length mechanism side

L2 

End cap length mechanism opposite side

 

„

Minimum distances

It is recommended to keep enough space for using the control 

mechanism or for maintenance.

In accordance with Articles 7 and 13 of EN 1366-2 respect the mini-

mum distances indicated below.

Summary of Contents for WK45 Series

Page 1: ...data the equipment and acces sories indicated could be subject to variations Installation booklet RECTANGULAR SERIES WK45 500 Pa 300 Pa Cert N 1812 CPR 1006 EN 15650 This is a 17 page installation bo...

Page 2: ...ling ve i o D B X H min 200 X 200 max 1500 X 800 B X H min 200 X 200 max 1500 X 800 B X H min 200 X 200 max 1500 X 800 EI 120 S Installation within vertical light wall gypsum blocks wall Wall minimum...

Page 3: ...sealing Wall minimum thickness 100 mm Wall minimum density 995 kg m Rock wool 140 kg m and endothermic varnish sealing ve i o W B X H min 200 X 200 max 1500 X 800 B X H min 200 X 200 max 1500 X 800 B...

Page 4: ...r In case of closed damper as a result of the action of the thermosen sitive element it is possible to manually reopen the damper by rotat ing the lever counterclockwise once the element has been repl...

Page 5: ...sing by remote control If power to the motor is cut off the blade will close Temperature calibration of thermosensitive element for auto matic damper closing 72 C 7 C Standard 95 C 9 C On request Fire...

Page 6: ...roswitch When the fire blade is closed the circuit is closed 3 NC contact of SA microswitch When the fire blade is open the circuit is open 4 NO contact of SA microswitch When the fire blade is open t...

Page 7: ...24V DC or 230 V AC version Motor 24V AC DC WK45VMB Belimo BFN24T Opening 4 W In stand by 1 4 W Motor 230V AC WK45DMB Belimo BFN230T Opening 5 W In stand by 2 1 W Motor 24V AC DC WK45VGB Belimo BF24T O...

Page 8: ...volving fire fighting compo nents must be carried out only by qualified personnel Only original spare parts supplied by the fire damper manufacturer must be used A functional test must be performed af...

Page 9: ...ntion fire resistance classification for transfer application is conform to section Fire resistance classification according to EN 13501 3 2009 limited to EI 120S if the ducted classification is high...

Page 10: ...k wool 100 kg m sealing 70 75 Yes One air duct Flexible wall EI 120 S Installation within vertical light wall plasterboard Mortar or plaster putty sealing 70 75 Yes Separate air duct EI 90 S Installat...

Page 11: ...ls floor of the same type but with greater thickness and or densi ty than those used in the test For plasterboard walls the test results are also valid for walls with a greater number of plasterboard...

Page 12: ...haped edges as indicated in the supplier s instruc tions and according to the following characteristics minimum thickness 70 or 100 mm according to the type and re sistance class required minimum dens...

Page 13: ...bove D2 Hole height see table above E Damper protrusion from the wall see table above Installations within vertical light wall plasterboard Refer to the section Construction supports characteristics f...

Page 14: ...provided in the wall as indicated in the table and in the drawing Damper positioning Position the damper in the opening so that the side of the closing mechanism extends as indicated in the table and...

Page 15: ...damper H Nominal height of the damper D1 Hole base see table above D2 Hole height see table above E Damper protrusion from the floor see table above S Floor minimum thickness see table above 1 Mortar...

Page 16: ...sealant 3 PROMASTOP E PASTE or HILTI CFS CT endothermic varnish Installation within floor with Fire Batt Weichschott sealing Refer to the section for further information Comply with the minimum dista...

Page 17: ...Hole height see table above E Damper protrusion from the floor see table above 1 Rock wool panel 50 mm thick with 140 kg m density 2 PROMASTOP E PASTE or HILTI CFS S ACR type sealant 3 PROMASTOP E PAS...

Reviews:

Related manuals for WK45 Series