April 27, 2004 Manual Version 1.01
7.13
Section 7.6
Configuring Control
The OmniLink II press control must be configured to allow the tonnage monitor module option. The
installation procedure is as follows:
1)
From the Main Menu screen, select the PRESS CONTROL softkey.
2)
Switch the RUN/PROG keyed selector switch to the PROG position.
3)
Select the CONFIGURE softkey and enter the Configuration Code.
4)
Select MACHINE PARAMETERS. The Machine Parameters menu will appear.
5)
Select the FACTORY CONFIG softkey. The Factory Parameters menu will appear.
6)
Position the cursor onto the parameter Tonnage Monitor, use the numeric keypad to change the
entry from 000 (OFF) to 001 (ON) and press ENT.
The Configuration Code gives limited access to change parameters in this screen. Only three
parameters that can be changed with the Configuration Code are Tonnage Monitor, Die
Protection, and Automatic Setup. The system will not allow the other parameters to be changed
with the Configuration Code.
7)
Exit back to the Main Operator Terminal screen.