T6 Setting Max. Winding Temperature
3.6.2 Higher-level temperature monitoring
The motors have an additional superior temperature monitoring by means of 2 Pt1000 temperature sensors,
which interrupts the power supply when the defined max. surface temperature is exceeded. The table below
must be consulted for setting the temperature relay.
Setting of Temperature Relais
Temperature class
Sensor
Max. surface temperature
T4
Pt1000
135 °C
T6
Pt1000
85 °C