Installation Guide C1251-2S preliminary
Page 16 of 22
0185-1173-E_2V0_IG_Drives_C1251-2S preliminary
NTI AG / LinMot
7
LED Blink Codes
LED Blink Codes
Error
Warn
EN
Description
Off
Warning
Operation
Enabled
Normal Operation:
Warnings and operation enabled are displayed.
On
● ~2Hz
0..15 x
Error Code
High Nibble
● ~2Hz
0..15 x
Error Code
Low Nibble
Error:
The error code is shown by a blink code with “WARN” and “EN”
The error byte is divided into low and high nibble (= 4 bit).
”WARN” and “EN” are blinking together.
The error can be acknowledged.
(e.g.: WARN blinks 3x, EN blinks 2x; Error Code = 32h)
● ~2Hz
● ~2Hz
0..15 x
Error Code
High Nibble
● ~2Hz
0..15 x
Error Code
Low Nibble
Fatal Error:
The error code is shown by a blink code with “WARN” and “EN”.
The error byte is divided into low and high nibble.
”WARN” and “EN” are blinking together.
Fatal errors can only be acknowledged by a reset or power cycle.
(e.g.: WARN blinks 3x, EN blinks 2x; Error Code = 32h)
● ~4Hz
● ~2Hz
0..15 x
Error Code
High Nibble
● ~2Hz
0..15 x
Error Code
Low Nibble
System Error:
Please reinstall firmware or contact support.
0-1s
1-2s
…
● ~0.5Hz
On
Signal Supply 24V too low:
The error and warn LEDs blink alternating if the signal 24V (X4.2) is less
than 18VDC.
0-250 ms
250-500ms
500-1000ms
…
Plug&Play Communication Active:
This sequence (Warn on, then En on, then both off, complete sequence of the 4
states ca. 1Sec) signalizes the state when the plug and play parameters are being
read from the motor.
0-125ms
125-250ms
…
Waiting for Defaulting Parameters:
When ID (S1, S2) is set to 0xFF, the drive starts up in a special mode and the Error
and Warn LED blink alternating ~4Hz. When the ID ist set to 0x00, all parameters
will be set to their default value. To leave this state, power down the drive and
change the ID. Also see in the Usermanual_LinMot-Talk under chapter trouble
shooting.
0-250ms
250-500ms
…
Defaulting Parameters Done:
When the parameters have set to their default values (initiated via S1/S2 on power
up) the Warn and En LEDs blink together at 2 Hz. To leave this state, power down
the drive. Also see in the Usermanual_LinMot-Talk under chapter trouble shooting.
Bootstrap
If also both RT LEDs are on, the drive is in the bootstrap mode. Set S5 to off.
The meaning of the error codes can be found in the
Usermanual_MotionCtrl_Software_SG5-SG7
and the user
manual of the installed interface software. These documents are provided together with LinMot-Talk
configuration software and can be downloaded from