25
•
Data B
- Select Data B for the above device. Depending on the device selected the Data used for testing may have special
properties. See above list.
•
Device C
- is what to control.
•
Data C
–
Set property for
Device C
. Syntax is used as follows:
•
RELAY
- These are relays on this Ultra. You can set up to four per schedule. Enter separated by commas, for example
"1,2,3,4"
•
FLAG
- This is a storage flag that can be used to make more complex schedules. There are 8 flags that can be turned on
or off.
•
REMOTE
- Refers to a remote Ultra 300 units. When these conditions are met, this Ultra will send a command to
control a remote Ultra 300. The Data field for a remote unit should be in the format, "REMOTE UNIT NUMBER, REMOTE
UNIT RELAY". For example, "3,5". These remote SERVERS must be identified in the page Configure/Remote Device
Config.
•
COUNTER
–
Add count to digital input counter
–
set as 1 or 2 depending which digital input is counting
•
BLUE LED
- No data.
•
- Will send eMail when condition meets.
•
NOTIFY
- Not Implemented.
•
Action
–
What to do with Device C. Options are:
•
ON
–
Turns device
ON
•
OFF
–
Turns device
OFF
•
TGL
–
Toggles
state of
Device C
•
RESET
–
Resets
Counters
Using the condition-
logic task builder, you can easily create tasks based on inputs or outputs’ status using IF…THEN… THAT
statement introduced above. Create up to three actions for each task providing you with the ultimate control and monitoring
solution for your project. Below is a typical use case to use the task builder for resetting the meter daily.