FAQ 

 

 

Does the EVO have Closed Loop Torque Control capability? 

ONLY EVO 8000 series can do Closed Loop Control, EVO 6000 and 6800 only supports SVVC and V/F 

 

Does the EVO have PM Motor Control capability?

 

PM motors require very precise timing and filters to operate without damaging motor. Only 8000 series 
have PM mode 

 

What is the recommended Fuse or Breaker size? 

It is recommended that a fast-acting current limiting Fuse is used because breakers may react too slow 
and damage the drive. Rules in the NEC specific to VFDs call for the breaker to be 125% of the INPUT 
current of the VFD (use rated current on the nameplate depending on the Duty Cycle) (for single phase 
input current, * 1.5 is the fuse size). 

 

What is the EVO’s voltage tolerance? 

EVO Voltage tolerances are +/- 15% 

 

Do we need Brake Kits AND a Braking Resistor? 

6000 needs kit and brake resistor to dissipate heat 

6800 just needs resistors, we have size recommendation if customer needs them 

 

What is the Maximum Overload Capacity (for dynamic Braking)? 

150% for 1 minute every 10 minutes. 

 

Can we disable Input Phase Loss Protection? 

Yes, set P7-00 to 0 (default is 1) 

 

 

 

Summary of Contents for EVO 6000

Page 1: ...QuickStart Guide _______________________________________________ EVO 6000 6800 ...

Page 2: ...iteon VFD QuickStart Guide This Quick Start guide tells you how to set up your EVO unit and use its basic features Please refer to the User Manual for the full specification and features Installation Direction EVO6000 ...

Page 3: ...EVO 6800 ...

Page 4: ...Basic Wiring Three Phase Input EVO6000 Single Phase Input EVO6800 ...

Page 5: ...Ex To change RPM press the MENU button to cycle between the RPM Display Parameters Menu and the Monitor Display Once on the RPM Display turn the Dial to desired speed and press in on the Dial to set the speed ...

Page 6: ...Factory Reset Make sure A1 01 is set to 2 default to give full access to all Parameters Ex For 60Hz 460V Set A1 03 to 2646 or 2623 for 60Hz 230V if uncertain use 2 wire seq ...

Page 7: ...T1 01 0 for rotational 1 or stationary 0 is default Change T1 12 to 1 and it will enter Autotune mode press Run to start the auto tune Display will show End when Autotune is complete Entering Initial Settings Manually ...

Page 8: ...Terminal Setup Operation Mode must be set to Terminal before terminal switches can be used Frequency Command must be set to 1 Analog Input before Pot can be used Terminal Descriptions ...

Page 9: ...EVO6000 EVO6800 7 5kW EVO6800 5 5kW ...

Page 10: ...Terminals Functions ...

Page 11: ...Analog Input can be changed using the parameters below Stopping and Accelerating Modes ...

Page 12: ...Relays Relays can be programmed to trigger under the condition listed below ...

Page 13: ...ct too slow and damage the drive Rules in the NEC specific to VFDs call for the breaker to be 125 of the INPUT current of the VFD use rated current on the nameplate depending on the Duty Cycle for single phase input current 1 5 is the fuse size What is the EVO s voltage tolerance EVO Voltage tolerances are 15 Do we need Brake Kits AND a Braking Resistor 6000 needs kit and brake resistor to dissipa...

Page 14: ...Main Circuit ...

Reviews: