background image

IP65

Twist off the cover

Push to unlock and 
remove  the board

4x

Lighting   direction

      Arrow sign in
   fitting base and
   label which show 
   lighting direction 
when the luminaire is 
       assembled

C

B3S

 fitting

Disassembling the C

B3S

 fitting

CB3S/3W/M3
CB3S/3W/ST
CB3S/3W/DALI

CB3S/6W/NM3

Fitting lighting direction

3

Technical Specification:

-

Supply Voltage: 220-240V AC 50/60Hz

-

Insulation Class: II

-

Ingress Protection: IP

65

-

Emergency Duration: 3

 h

ours

-

Light Source:

 for M3 and ST version

 

3

for NM3 version 6W 

LED

for DALI version 3W

-

Battery 6.4V 

3.

0Ah LiFEPO4 for 

3W 

M3 & ST

Battery 6.4V 

6.

0Ah LiFEPO4 for 

6W N

M3 & ST

Battery 9.6V 1.5Ah LiFEPO4 for DALI

-

Battery Recharge Time: 12h

-

Max Battery Temperature: 55°C

-

Ambient Temperature: 0 - 40°C

-

Charge indicator: Green / Red LED

-

Deep Discharge Protection DDP

-

Self-Test & DALI versions available

-

Surface assembly (

wall, 

ceiling)

-

Assembly indoors to flat surface

-

Polycarbonate body

-

Maintained or Non-Maintained Operation

Important:

It is recommended that the unit is installed by a competent person 
ensuring the installation complies with the necessary standards. The 
company accept no responsibility for incorrect installation, operation 
or maintenance. The unit requires an unswitched supply for charging 
the  battery  and  a  switched  supply  for  a  maintained  unit.  After 
installation of the fitting, the battery must be charged for 24 hours. 

LED indication Chart

Testing / Commissioning:

Ensure the load is connected
Enter  the  commissioning  date  on  battery  pack

  and 

onnect  the 

battery
Switch on the unswitched supply – Check that the green charge LED 
illuminates
Switch on the maintained supply – Check that the fitting illuminates as 
normal
Switch off the maintained supply
Switch off the unswitched supply – Check that the green charge led 
extinguishes and the fitting illuminates
Switch on the unswitched supply

It is recommended that the batteries are renewed  every 6 years.
The fitting is equipped with non-replaceable LED.

Self-Test Function:

A Function Test automatically runs every 28 days. During this test the 
fitting is switched into emergency mode for 1 minute. During the test 
the battery discharge current is checked.
A Full Duration Test automatically runs every 364 days. During this 
test the fitting is switched into emergency mode for 3 hours . During 
the test the battery discharge current and battery voltage is checked

c