IP65
Twist off the cover
Push to unlock and
remove the board
4x
Lighting direction
Arrow sign in
fitting base and
label which show
lighting direction
when the luminaire is
assembled
C
B3S
fitting
Disassembling the C
B3S
fitting
CB3S/3W/M3
CB3S/3W/ST
CB3S/3W/DALI
CB3S/6W/NM3
Fitting lighting direction
3
Technical Specification:
-
Supply Voltage: 220-240V AC 50/60Hz
-
Insulation Class: II
-
Ingress Protection: IP
65
-
Emergency Duration: 3
h
ours
-
Light Source:
for M3 and ST version
3
W
for NM3 version 6W
LED
for DALI version 3W
-
Battery 6.4V
3.
0Ah LiFEPO4 for
3W
M3 & ST
Battery 6.4V
6.
0Ah LiFEPO4 for
6W N
M3 & ST
Battery 9.6V 1.5Ah LiFEPO4 for DALI
-
Battery Recharge Time: 12h
-
Max Battery Temperature: 55°C
-
Ambient Temperature: 0 - 40°C
-
Charge indicator: Green / Red LED
-
Deep Discharge Protection DDP
-
Self-Test & DALI versions available
-
Surface assembly (
wall,
ceiling)
-
Assembly indoors to flat surface
-
Polycarbonate body
-
Maintained or Non-Maintained Operation
Important:
It is recommended that the unit is installed by a competent person
ensuring the installation complies with the necessary standards. The
company accept no responsibility for incorrect installation, operation
or maintenance. The unit requires an unswitched supply for charging
the battery and a switched supply for a maintained unit. After
installation of the fitting, the battery must be charged for 24 hours.
LED indication Chart
Testing / Commissioning:
Ensure the load is connected
Enter the commissioning date on battery pack
and
onnect the
battery
Switch on the unswitched supply – Check that the green charge LED
illuminates
Switch on the maintained supply – Check that the fitting illuminates as
normal
Switch off the maintained supply
Switch off the unswitched supply – Check that the green charge led
extinguishes and the fitting illuminates
Switch on the unswitched supply
It is recommended that the batteries are renewed every 6 years.
The fitting is equipped with non-replaceable LED.
Self-Test Function:
A Function Test automatically runs every 28 days. During this test the
fitting is switched into emergency mode for 1 minute. During the test
the battery discharge current is checked.
A Full Duration Test automatically runs every 364 days. During this
test the fitting is switched into emergency mode for 3 hours . During
the test the battery discharge current and battery voltage is checked
c