background image

INSTALLATION INSTRUCTIONS

CAUTION:

A potential electrical shock hazard exists even
when AC power supply has been turned off.
Disconnect Battery connector before servicing
fixture. Do not remove the wire harness con-
nector when AC power is present.

APPROXIMATE WORKING VOLTAGE

Battery Pack input: 120 OR 277V AC

IMPORTANT SAFEGUARDS

WARNING: FAILURE TO FOLLOW THESE INSTRUCTIONS AND WARNINGS MAY RESULT IN DEATH, SERIOUS INJURY
OR SIGNIFICANT PROPERTY DAMAGE –

For your protection, read and follow these warnings and instructions carefully before installing or maintaining this equip-
ment. These instructions do not attempt to cover all installation and maintenance situations. If you do not understand
these instructions or additional information is required, contact Lithonia Lighting or your local Lithonia Lighting distributor.

WARNING: RISK OF ELECTRIC SHOCK – NEVER CONNECT TO, DISCONNECT FROM OR SERVICE WHILE EQUIP-
MENT  IS ENERGIZED.

WARNING: RISK OF FIRE – Lamps are hot. Keep combustibles material away from hot parts. Observe lamp
manufacturer’s warnings, recommendations and restrictions on lamp operation and maintenance. Make sure lamps are
correctly installed.

WARNING: DO NOT USE ABRASIVE MATERIALS,  OR OTHER SOLVENTS. USE OF THESE SUBSTANCES MAY DAMAGE
FIXTURE, WHICH MAY RESULT IN PERSONAL INJURY.

WARNING: RISK OF PERSONAL INJURY – This product may have sharp edges. Wear gloves to prevent cuts or abrasions
when removing from carton, handling, installing and maintaining this product. (WHERE APPLICABLE)

Before wiring to power supply, turn off electricity at fuse or circuit breaker.

Disconnect A.C. power and unplug battery before servicing.

Consult your local building code for approved wiring and installation.

Do not use outdoors.

Do not let power supply cord touch hot surfaces.

Do not mount near gas or electric heater.

Do not install a damaged fixture.

This product must be installed in accordance with the applicable installation codes and ordinances.

Proper grounding is required to ensure personal safety. (WHERE APPLICABLE)

All service shall be performed by qualified service personnel. This product must be installed and maintained in accor-
dance with the applicable installation codes by a person familiar with the construction and operation of the product and
the hazards involved.

Equipment should be mounted in locations and at heights where it will not readily be subjected to tampering by unautho-
rized personnel.

The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.

Do not use this equipment for other than intended use.

SAVE THESE INSTRUCTIONS

READ  AND FOLLOW ALL SAFETY INSTRUCTIONS

FIELD INSTALLABLE FLUORESCENT BATTERY
PACK IS UNIVERSALLY COMPATIBLE WITH THE
BALLASTS AND OPERATING LAMP(S) IN THE
LAMP COMPATIBILITY TABLE (PAGE 3).

IMPORTANT NOTES:
Make sure that branch circuit feeds are derived from
a common phase for both normal lighting ballast and
Battery Pack prior to installation.

Notice: To ensure proper grounding, mount unit only
with metal cutting screws (not provided).

The Battery Pack  can be used with a switched or
unswitched (night) circuit. When used with a switched
fixture it is important to note that the power to the
Battery Pack must be provided by an unswitched
circuit.

EMERGENCY FLUORESCENT BATTERYPACK

Model EI500

Summary of Contents for EI500

Page 1: ...tricity at fuse or circuit breaker Disconnect A C power and unplug battery before servicing Consult your local building code for approved wiring and installation Do not use outdoors Do not let power supply cord touch hot surfaces Do not mount near gas or electric heater Do not install a damaged fixture This product must be installed in accordance with the applicable installation codes and ordinanc...

Page 2: ...erform all test required by local codes 1 Check equipment rating to be sure that fixture will receive proper line voltage 2 Be sure pilot light is on If pilot light does not operate check to see that A Pilot Light Connector and test switch c are con nected B AC power is on C Voltage on branch circuit to Battery Pack is rated at line voltage 120V or 277V If no line voltage can be measured locate pr...

Page 3: ...T NOTES Before connectingTS PL connector or wiring unit to fixture refer to INSTALLATION PROCEDURE and IMPORTANT SAFEGUARDS for safety information and mounting procedures Page 3 TWO LAMP RAPID START BALLAST FIGURE B ONE LAMP INSTANT START SLIMLINE BALLAST FIGURE C ...

Page 4: ...Page 4 TWO LAMP LEAD LAG INSTANT START SLIMLINE BALLAST FIGURE D TWO LAMP SERIES LEAD BALLAST TWO LAMP INSTANT START BALLAST FIGURE F FIGURE E ...

Page 5: ...FIGURE G Page 5 THREE LAMP RAPID START BALLAST THREE LAMP INSTANT START BALLAST FIGURE H ONE LAMP WITHOUT AC BALLAST FIGURE I ...

Page 6: ...Page 6 ONE LAMP INSTANT START BALLAST FIGURE J ONE LAMP CIRCLINE BALLAST FIGURE K FOUR LAMP INSTANT START ELECTRONIC BALLAST FIGURE L ...

Page 7: ...e of invoice Our guarantee covers any defect in manufacturing provided the defect develops under normal and proper use This liability does not include lamps and extends only to repair or replacement of the defective part and labor charges for correction of the defect by repair or replacement These labor charges will be paid by Lithonia Lighting only with prior written authority has been granted by...