PGR-3100 Ground-Fault Indication System

1.  FEATURES

 

Green LED’s indicate presence of voltage to ground for   

  each phase of a power system. 
 

   A ground fault (or phase loss) is indicated when a set  

    of LED’s is off.

 

   LED’s are on when phase-to-ground voltage exceeds  

    30 Vac.

 

   Redundant LED’s are used for reliability.

• Pressing LAMP TEST causes all LED’s to light.

NOTE:

  The  LAMP  TEST  feature  requires  an  isolated                  

120 Vac supply.
• Direct connection for voltages up to 600 Vac line to line.
 

   Potential transformers (PT’s) are required for voltages  

    greater than 600 Vac.

• Provides faulted-phase indication for resistance-grounded  

  systems and ungrounded systems.

2. DESCRIPTION

 

The PGR-3100 is a self-powered ground-fault indication 

system. Presence of phase-to-ground 

voltage is indicated by redundant LED’s (two per phase).  

The respective phase LED’s are off when phase-to-ground 

voltage is less than 30 Vac. The PGR-3100 meets the 

National Electrical Code requirements for ground detectors 

for ungrounded alternating-current systems as defined 

in NEC 250.21. It also meets the Canadian Electrical Code 

requirements for ungrounded alternating-current systems in 
accordance with CEC 10-106(2).

3.  INSTALLATION

 

Outline and panel-mounting details are shown in Fig.1.

  For 208- to 600-Vac systems, connect the PGR-3100 directly 

to the three-phase bus. For 208- or 240-volt installations, use 

terminals AL, BL, and CL. For systems above 240 V and up to 

600 V use terminals AH, BH, and CH.  See Figs. 2 and 4.
  For systems above 600 V, install PT’s as shown in Figs. 3 

and 5.
  Connect terminal G and chassis-bonding terminal ( )              

to ground.
  For LAMP TEST connect 120 Vac supply to terminals L and 

G. Connection and use of LAMP TEST circuit is optional.

AH

POWR-GARD

GROUND-FAULT INDICATION SYSTEM

PGR-3100

SERIES

A

B

C

LAMP TEST

GROUND FAULT PRESENT WHEN
ANY INDICATOR OFF

AL

BH

BL

CH

CL

Rev:  

Phase Voltage:
Phase Current:

Lamp-Test Supply:

208-600 Vac,  50/60 Hz

50 mA Maximum

1 VA, 120 Vac 50/60 Hz

PGR-3100

GROUND-FAULT INDICATION SYSTEM

Serial No:

00

ELXXXXYYYYY

1-800-TEC-FUSE (1-800-832-3873)

Made in Saskatoon, Canada

LR  53428

US

C

R

108.0
(4.25)

95.3

(3.75)

76.2

(3.0

0)

88.9

(3.50)

6.4

(0.25)

95.3

(3.75)

6.4

(0.25)

76.2

(3.0

0)

101.6

(4.00)

69.9

(2.75)

3.2

(0.1

3)

FACEPLATE OUTLINE

4.0 (0.16) DIA

6.4 (0.25) R

MOUNTING DETAIL

FRONT

SIDE

52.4

(2.06)

 

FIGURE 1.  PGR-3100 Outline and Mounting Details. 

Summary of Contents for PGR-3100

Page 1: ...00 832 3873 E mail techline littelfuse com www littelfuse com PGR 3100 Copyright 2018 Littelfuse All rights reserved Document P95 EPI0 00000 PGR 3100 MANUAL GROUND FAULT INDICATION SYSTEM Revision 6 A...

Page 2: ...Page i REV 6 A 060818 PGR 3100 Ground Fault Indication System This page intentionally left blank...

Page 3: ...ed 240 to 600 V System 2 3 Connection Diagram for Ungrounded Systems above 600 V 2 4 Connection Diagram for Resistance Grounded System up to 600 V 3 5 Connection Diagram for a Resistance Grounded Syst...

Page 4: ...Page iii REV 6 A 060818 PGR 3100 Ground Fault Indication System This page intentionally left blank...

Page 5: ...ets the Canadian Electrical Code requirements for ungrounded alternating current systems in accordance with CEC 10 106 2 3 INSTALLATION Outline and panel mounting details are shown in Fig 1 For 208 to...

Page 6: ...MS UPTO 240 V USE H TERMINALS FOR SYSTEMS ABOVE 240 V UPTO 600 V TRANSFORMER ENCLOSURE SERVICE ENCLOSURE A B C 1 A 1 A 1 A AL AH BL BH CL CH L G 120 V LAMP TEST PGR 3100 GROUND FAULT INDICATION SYSTEM...

Page 7: ...BOVE 240 V AND UPTO 600 V NOTE 1 TRANSFORMER ENCLOSURE SERVICE ENCLOSURE A B C 1 A 1 A 1 A AL AH BL BH CL CH 120 V LAMP TEST PGR 3100 GROUND FAULT INDICATION SYSTEM L G NEUTRAL GROUNDING RESISTOR PT S...

Page 8: ...imum LED Threshold 30 Vac minimum Dielectric Strength 2 200 Vac 1 minute Shipping Weight 0 3 kg 0 8 lb Dimensions Height 108 mm 4 3 Weight 88 9 mm 3 5 Depth 54 mm 2 1 Environment Operating Temperature...

Page 9: ...LEASE DATE MANUAL REVISION PRODUCT REVISION REVISION NUMBER ON PRODUCT LABEL June 08 2018 6 A 060818 03 March 09 2012 6 APPENDIX A PGR 3100 REVISION HISTORY MANUAL REVISION HISTORY REVISION 6 A 060818...

Reviews: