7
WIRING
s
!
WARNING
Check local electrical and
building codes before installation. The installation must be in
accordance with their regulations as well as the most recent
National Electrical Code (NEC).
Check the pump label for proper voltage required. Do not connect to
voltage other than that shown.
A ground fault circuit interrupter (GFCI) is required.
The pump should be connected or wired to its own circuit with
no other outlets or equipment in the circuit line. The fuses and
circuit breaker should be of ample capacity in the electrical circuit.
See table below:
s
!
WARNING
The flexible jacketed cord assembly
mounted to the pump must not be modified in any way, with the
exception of shortening the cord to fit into a control panel. Any splice
between the pump and the control panel must be made within a
junction box and mounted outside of the basin, and comply with
the National Electrical Code. Do not use the power cord for lifting
the pump.
SPECIFICATIONS
Gallons Per Minute, at Height
Liters Per Minute, at Height
Shut-Off
5'
1.5 m
10'
3 m
15'
4.5 m
20'
6.1 m
30'
9.1 m
6EC
53
50
42
34
-
28'
201
189
159
129
8.5 m
10EC
67
57
47
42
24
36'
254
216
178
159
91
11 m
W A R N I N G
W A R N I N G
MANUAL
WHITE
WHITE
BLUE
RED
WHITE
BLACK
GREEN
SWITCH
WHITE
WHITE
WHITE
RED
BLUE
BLACK
GREEN
CAP
CAP
6EC/10EC SERIES
AUTOMATIC
MANUAL
MANUAL
WHITE
WHITE
BLUE
RED
WHITE
BLACK
GREEN
SWITCH
WHITE
WHITE
WHITE
RED
BLUE
BLACK
GREEN
CAP
CAP
6EC/10EC SERIES
AUTOMATIC
AUTOMATIC
Pump
HP
Voltage
Breaker Amps
6EC
1/3
115 V
15
10EC
1/2
115 V
15