LXC706 Series Genset Controller
Dongguan Tuancheng Automation Equipment Co.,Ltd.
LXC706 Product User Manual
Donggua
n Tuancheng Automation Equipment Co.,
Ltd.
:
+86-769-23836636
:
F:+86-769-23166296
:
www.lixise.com
Page 10 of 17
P07
Start idle time
(0-3600)S
0s
This is the amount of time that the start Idle speed is
held active.These allow the engine to hold low speed.
P08
Warming up
delay
(0-3600)S
10s
P09
Cooling delay
(0-3600)S
10s
P10
Stop idle time
(0-3600)S
0s
This is the amount of time that the stop Idle speed is
held active. These allow the engine to hold low speed.
P11
ETS solenoid
hold
(0-120)S
20s
This timer is used if the unit is configured to operate an
Energize to stop engine. It dictates the duration that
the ETS output will remain active after the module has
detected the engine has come to rest. If the ETS
output is not configured, this timer will still operate,
preventing an immediate restart.
P12 Fail to stop delay
(0-120)S
0s
Once the module has given a shutdown signal to the
engine it expects the engine to come to rest. It
monitors the Oil pressure and speed sensing sources
and if they still indicate engine movement when this
timer expires a ‘Fail to stop’ alarm signal is generated.
P13 Flywheel Teeth
(100-300)
118
Tooth number of the engine, for judging of starter
crank disconnect conditions and inspecting of engine
speed. See the installation instructions.
P14
Poles
(2-16)
4
P15 Gen Abnormal
Delay
(0-20.0)s
10.0s
The alarm delay of generator over voltage and under
voltage.
P16
Gen Over
Voltage
(30-620)V
264V
When generator voltage has exceed the set value and
the “Gen abnormal delay” has expired, Gen Over
Voltage is active. When set the value as 620V, the
controller does not detect over voltage signal.
P17 Generator Under
Voltage
(30-620)V
196V
When generator voltage has fallen below the set value
and the “Gen abnormal delay” has expired, Gen Under
Voltage is active. When set the value as 30V, the
controller does not detect under voltage signal.
P18
Over Speed
(0-6000)RPM 1710RPM
When engine speed has exceed the set value for 2s,
Over Speed is active. It will initiate a shutdown alarm
signal.
P19
Under Speed (0-6000)RPM 1200RPM
When engine speed has fallen below the set value for
10s, Under Speed is active. It will initiate a shutdown
alarm signal.
P20 Over Frequency (0-75.0)Hz
57.0Hz
When generator frequency has exceed the set value
for 2s, Over Frequency is active. It will initiate a
shutdown alarm signal.
P21
Under
Frequency
(0-75.0)Hz
45.0Hz
When generator frequency has fallen below the set
value but Not equal to 0 for 10s, Under Frequency is
active. It will initiate a shutdown alarm signal.
P22
Charge Alt
Failure
(
Warning
)
(0-30.0)V
6.0V
During generator is normal running, when alternator
D+(WL) voltage has fallen below the set value and
remains for 5s, It will initiate a shutdown alarm signal.
(
Return value is 1V
)
.
P23
Battery Over
Voltage
(
Warning
)
(12.0-40.0)V
33.0V
When battery voltage has exceeds the set value and
remains for 20s, It will initiate a warning alarm signal.
Only warning and not to shutdown the generator.
(
Return value is 1V
)
.