LXC706 Series Genset Controller
Dongguan Tuancheng Automation Equipment Co.,Ltd.
LXC706 Product User Manual
Donggua
n Tuancheng Automation Equipment Co.,
Ltd.
:
+86-769-23836636
:
F:+86-769-23166296
:
www.lixise.com
Page 9 of 17
Emergency Stop:
When emergency stop input, ETS solenoid stop immediately output, and
then fuel disconnect, preheat and start signal emit emergency stop alarm signal.
Gen Over Voltage:
When the continuous sampling voltage higher than the preset value, at
the end of the abnormal delay, signal generator voltage is too high, outage alarm at the
same time.
Gen Under Voltage:
When sampling the voltage is lower than the preset value continuously,
at the end of the abnormal delay signal generator voltage is too low, outage alarm at the
same time.
Gen Over Frequency:
When the sampling frequency for 10 seconds after the signal
generator frequency is too high, outage alarm at the same time.
Gen Under Frequency:
When the sampling frequency for 2 seconds after the signal
generator frequency is too low, outage alarm at the same time.
Common Alarm:
when any alarm or warn is appear, this alarm will active. When the over
speed, under speed, high temperature, low oil pressure, emergency stop, no generator,
crank failure, stop failure alarm, battery over voltage, battery under voltage, common alarm
LED illuminate, and common alarm output.
7. PARAMETERS TABLE(ONLY ADJUST VIA PC)
7.1. PARAMETER SETTING LIST (TABLE I)
Set the content as follows:
NO.
Parameter
Range
Default
Description
P00
Start delay
(0-3600s)
1s
It’s the delay from remote start signal is active or
mains is failure, to start generator.
P01
Stop delay
(0-3600s)
1s
It’s the delay from remote start signal is inactive or
mains is normal, to stop generator.
P02
Number of
Crank
(1-9)
3
Numbers of crank cycles.
P03
Preheat time
(0-300)S
0s
This timer dictates the duration that the pre-heat
output will be active before an attempt is made to start
the engine. Once this timer has expired cranking will
commence.
P04 Cranking time
(1-60)S
8s
This is the maximum amount of time that the module
will energize the starter motor for during starting
attempts once the starter has engaged.
P05
Crank rest
time
(3-60)S
10s
This is the amount of time the module will wait for
between start attempts.This is to allow the starter
motor to cool and the starter batteries to recover.
P06
Safe running
time
(1-60)S
10s
This timer dictates how long the module will ignore the
Low oil pressure, High Engine Temperature, Under
speed, Under volts and any other inputs configured as
active from safety on.