14 (15)

EN.33.C.94.1702

Troubleshooting

Measures requiring tools should be carried out by a qualified installer. Begin troubleshooting by viewing 

the status indicators, see item 10, and 

Control panel

.

Fault

Possible cause

Remedial messure

Operation and status 

indicator not illumina-

ted, no heat. 

Electric boiler without power. 

Check main fuses. 

Main switch turned off. 

Turn main switch to position 1. Connection delay switches off 

output if boiler without power longer than 3 minutes. 

Operation indicator 

illuminated and status 

indicator not illumina-

ted, no heat. 

Selector switch in position: 

Select an operation mode. 

Low initial value. 

Initial value below 15 °C, i.e. no need for heating. 

Thermostat valve / valves in radiator 

system or room thermostat of floor-

based heating system set for low 

temperature. 

Set thermostat valve / valve or room thermostat to desired 

temperature. 

Operation and status 

indicator illuminated, 

no heat or not enough 

heat. 

Incorrectly set regulators. 

Check selections regarding heating graph, transition heating 

graph, maximum temperature and night-time temperature 

drop. Check selector setting. 

Overheating (maximum safe tempe-

rature) protection function has been 

triggered. 

If overheating (maximum safe temperature) protection 

function has been triggered, check functioning of circulation 

pump and valves. Reset by pressing overheating (maximum 

safe temperature) protection button down after temperature 

has dropped below 80 °C. 

Electric boiler fun-

ctions normally, but not 

enough heat. 

Counter-pressure in heating system 

has exceeded overflow valve’s ope-

ning pressure. 

Check heating system’s counter-pressure. Contact plumber. 

Electric boiler’s group 

fuses blown. 

Electric cartridge damaged. 

Check electric cartridge’s isolation. If electric cartridge has to 

be replaced, it is important to separate the loops in order to 

avoid sound of boiling alarm. 

Water leaks out from 

air-bleeder. 

Impurities in air-bleeder or broken 

air-bleeder. 

Replace or clean air-bleeder. 

Resistance values of boiler’s temperature sensor

NOTE!

 The sensor must not be connected to the circuit 

board while readings are taken. 

Boiler/Outgoing water temperature sensor
0 ºC

R(Ω)

0 ºC

R(Ω)

32,7 k 

50 

3,6 k 

25,4 k 

55 

3,0 k 

10 

19,9 k 

60 

2,5 k 

15 

15,7 k 

65 

2,1 k 

20 

12,5 k 

70 

1,8 k 

25 

10,0 k 

75 

1,5 k 

30 

8,1 k 

80 

1,3 k 

35 

6,5 k 

85 

1,1 k 

40 

5,3 k 

90 

915 

45 

4,4 k 

95 

787 

Outside temperature sensor
0 ºC

R(Ω)

0 ºC

R(Ω)

-35 

64,2 

±0 

8,0 

-30 

47,0 

6,8 

-25 

34,7 

10 

5,3 

-20 

25,9 

15 

4,2 

-15 

19,5 

20 

3,4 

-10 

14,8 

25 

2,7 

-5 

11,4 

30 

2,2 

Assembly instructions | LK Electric Boiler 11-n

Summary of Contents for 11-n

Page 1: ...erflow valve safety valve device to pre vent overheating if low flow rates it activa tes maximum safe temperature protection Circulation pump Grundfos UPM3 15 40 Enclosure concealing pipe connections...

Page 2: ...tridge 25 Skirt concealing pipe connections 13 14 15 12 23 17 18 22 3 19 25 1 2 5 4 8 7 6 9 16 18 20 17 11 14 13 24 12 22 21 10 Ben mning 1 Safety valve 2 5 bar female 2 Automatic air bleeding valve m...

Page 3: ...stallation The space between the floor and the boiler base must be at least 600 mm to allow electric cartrid ges to be replaced The connection of the boiler and the heating sys tem must be in accordan...

Page 4: ...ESSURE CURVE 3 CONST CURVE KURVA 1 CONST CURVE KURVA 2 CONST CURVE KURVA 3 CONST CURVE KURVA 4 If the button is depressed for 2 sec the pump switches to setup mode and the LEDs flash In setup mode any...

Page 5: ...d To avoid this an overflow valve is built in ensuring flow though the boiler If the pressure resistance of the heating system ex ceeds the overpressure flow problems can arise in the heating system F...

Page 6: ...from the fuses and must be protected Connection is made to the base of the circuit board using high current insulated cable minimum 0 75 mm2 The earth grounding is connected using terminal 4 The trans...

Page 7: ...acity corresponds to 7 9 kW When applying voltage based control 0 10V DC 10V is needed for connecting five levels The same applies to the voltage signal for con nected capacity Delay in connection fol...

Page 8: ...put Groups 1 and 2 as well as 3 x 2 1 kW for Output Group 3 Wiring diagram 1 2 3 4 5 6 7 8 9 10 11 12 13 14 18 15 19 19 17 16 BLACK BLACK BLACK BLACK WHITE WHITE WHITE WHITE WHITE WHITE BROWN BROWN BR...

Page 9: ...11 kW Fuse Fuse Fuse Fuse Fuse Output level Output Cur rent L1 Cur rent L2 Cur rent L3 Output group kW A A A 1 15 1 6 3 9 3 9 0 1 2 30 3 1 3 9 3 9 7 8 2 3 45 4 7 6 8 6 8 6 8 1 2 4 55 6 3 9 1 9 1 9 1 3...

Page 10: ...ning main switch to position O if the purpose is to switch off the boiler Heating system needs to be filled with water The circulation pump is set in motion and protection against freezing is activate...

Page 11: ...atus indicator is illuminated steadily Loss of pressure No voltage or selector in position UTK panel 15 14 13 11 12 The panel is viewable once the boiler s top support has been taken off and the autom...

Page 12: ...f the system s pressure drops and does not rise fill it up with water until the pressure gauge shows approx 2 bar Repeated problems in main taining the pressure may be an indication of a leak in the s...

Page 13: ...s indicated by the flashing of the status indicator see item 10 and Control panel Overheating maximum safe temperature protection The electric boiler s overheating maximum safe temperature protection...

Page 14: ...ion has been triggered If overheating maximum safe temperature protection function has been triggered check functioning of circulation pump and valves Reset by pressing overheating maximum safe temper...

Page 15: ...ditional power consumption In standby mode PSB 0 003 kW Standby heat loss Pstby 0 022 kW Outside temperature compensator UTK E Class II 2 contribution to Season medium efficiency Recycling After disma...

Reviews: