EN.33.C.94.1702

Assembly instructions | LK Electric Boiler 11-n

Where the pressure or temperature is reduced, 

the vessel will be able to handle larger heating 

system volumes.

Glycol anti-freeze mixtures reduce the capacity of 

the expansion vessel. Contact LK for advice.

Safety valve

The safety valve opens at 2.5 bar. A drainpipe 

should be fitted and connected to a waste outlet.

Circulation pump

Delivery setting: Constant pressure curve 1. 

If parts of the heating system do not get hot, 

this can be changed to Constant pressure curve 

2. Selecting a higher curve increases energy con-

sumption and operating costs.

Push but-

ton

LEDs

In operating mode, the first LED lights up green, 

and between one and four LEDs light up yellow. 

The yellow LEDs indicate the operating capacity 

of the pump.

0 - 25 %

25 - 50 %

50 - 75 %

75 - 100 %

Pressing the button displays the pump setting for 

2 sec before the pump returns to normal display.

Pipe installation

The electric boiler is mounted indoors, with the 

pipe connections at the bottom.

Current building standards and plumbing regu-

lations must be followed during installation.

The space between the floor and the boiler base 

must be at least 600 mm to allow electric cartrid-

ges to be replaced.

The connection of the boiler and the heating sys-

tem must be in accordance with the system dia-

gram below.

Ambient room temperature must not exceed 

 

30 ºC.

The boiler is designed for use in sealed systems. 

Hard, (calcium-rich) water is not suitable for the 

boiler. “Hard” water calcium deposits may da-

mage the boiler; in very hard water areas, water 

softeners may be required, check the pH value 

is not low – pH7 is neutral. Note: high Chlorine 

water treatment levels may damage parts of the 

boiler, particularly the heating cartridges.

When connecting external pipe work to the boi-

ler, care must be taken not to bend or damage the 

boilers internal pipe work.

Isolation valves must be mounted between the 

electric boiler and the heating system to simplify 

filling and draining. 

All pipe connectors are 1” female.

Expansion vessel

The vessels capacity is 12 litres and is pre-pres-

surised at 1.5 bar, which corresponds to a static 

height of 15 metres. At 1.5 bar, the expansion ves-

sel can handle heating system volume of 200 lit-

res, with a boiler temperature of 60 °C.

When supplied, the expansion vessel is pres-

surised at 1.5 bar. This may require adjustment 

during installation.

Summary of Contents for 11-n

Page 1: ...erflow valve safety valve device to pre vent overheating if low flow rates it activa tes maximum safe temperature protection Circulation pump Grundfos UPM3 15 40 Enclosure concealing pipe connections...

Page 2: ...tridge 25 Skirt concealing pipe connections 13 14 15 12 23 17 18 22 3 19 25 1 2 5 4 8 7 6 9 16 18 20 17 11 14 13 24 12 22 21 10 Ben mning 1 Safety valve 2 5 bar female 2 Automatic air bleeding valve m...

Page 3: ...stallation The space between the floor and the boiler base must be at least 600 mm to allow electric cartrid ges to be replaced The connection of the boiler and the heating sys tem must be in accordan...

Page 4: ...ESSURE CURVE 3 CONST CURVE KURVA 1 CONST CURVE KURVA 2 CONST CURVE KURVA 3 CONST CURVE KURVA 4 If the button is depressed for 2 sec the pump switches to setup mode and the LEDs flash In setup mode any...

Page 5: ...d To avoid this an overflow valve is built in ensuring flow though the boiler If the pressure resistance of the heating system ex ceeds the overpressure flow problems can arise in the heating system F...

Page 6: ...from the fuses and must be protected Connection is made to the base of the circuit board using high current insulated cable minimum 0 75 mm2 The earth grounding is connected using terminal 4 The trans...

Page 7: ...acity corresponds to 7 9 kW When applying voltage based control 0 10V DC 10V is needed for connecting five levels The same applies to the voltage signal for con nected capacity Delay in connection fol...

Page 8: ...put Groups 1 and 2 as well as 3 x 2 1 kW for Output Group 3 Wiring diagram 1 2 3 4 5 6 7 8 9 10 11 12 13 14 18 15 19 19 17 16 BLACK BLACK BLACK BLACK WHITE WHITE WHITE WHITE WHITE WHITE BROWN BROWN BR...

Page 9: ...11 kW Fuse Fuse Fuse Fuse Fuse Output level Output Cur rent L1 Cur rent L2 Cur rent L3 Output group kW A A A 1 15 1 6 3 9 3 9 0 1 2 30 3 1 3 9 3 9 7 8 2 3 45 4 7 6 8 6 8 6 8 1 2 4 55 6 3 9 1 9 1 9 1 3...

Page 10: ...ning main switch to position O if the purpose is to switch off the boiler Heating system needs to be filled with water The circulation pump is set in motion and protection against freezing is activate...

Page 11: ...atus indicator is illuminated steadily Loss of pressure No voltage or selector in position UTK panel 15 14 13 11 12 The panel is viewable once the boiler s top support has been taken off and the autom...

Page 12: ...f the system s pressure drops and does not rise fill it up with water until the pressure gauge shows approx 2 bar Repeated problems in main taining the pressure may be an indication of a leak in the s...

Page 13: ...s indicated by the flashing of the status indicator see item 10 and Control panel Overheating maximum safe temperature protection The electric boiler s overheating maximum safe temperature protection...

Page 14: ...ion has been triggered If overheating maximum safe temperature protection function has been triggered check functioning of circulation pump and valves Reset by pressing overheating maximum safe temper...

Page 15: ...ditional power consumption In standby mode PSB 0 003 kW Standby heat loss Pstby 0 022 kW Outside temperature compensator UTK E Class II 2 contribution to Season medium efficiency Recycling After disma...

Reviews: