| Instruction Manual

1

  

LK 810 ThermoMat 2.0 G

  

TECHNICAL DATA

Voltage

230 VAC 50 Hz 

Power consumption

5-52 W, depending on pump speed

Max. boiler efficiency

65 kW at 20 °C ΔT

Return temperature

55 °C, 60 °C, 65 °C or 70 °C

Working temperature

Min. 5 °C/Max. 110 °C 

Ambient temp.

Min. 0 °C/Max. 70 °C

Max. working pressure 0.6 MPa (6 bar)
Media

Water - Glycol mixture max. 50%

Thread standard

Rp - female thread

Circulating pumps

Grundfos UPM3 AUTO L xx-70

Material, valve body

Brass EN 1982 CB753S

Material, insulation

Expanded Polypropylene EPP

  

 

 

   

    LK 810 ThermoMat 2.0 G is a loading unit for heating  applications 
with solid fuel boilers and storage tanks. The  loading unit is in-
tended to ensure a high return temperature as well as an optimal 
temperature stratification in the storage tank, thus increasing the 
efficiency of the system. Tarring and  condensation are prevented 
which prolongs boiler life.
    

CIRCULATING PUMP

Four pump positions are available depending on boiler capacity.
It is to be noted that the maximum capacity of a boiler may be 
higher than its nominal capacity.

FUNCTION OF THE BACKFLOW PREVENTER

LK 810 ThermoMat 2.0 G Eco loading unit has, depending on 
model, a backflow preventer which automatically opens for self-
circulation when the pump stops. The backflow preventer has the 
following functions:

1.

 After the fire has gone out and the circulating pump has stopped 

the remaining hot water will selfcirculate to the storage tank.

2. 

In case of power failure the hot water will self-circulate to the tank.

3.

 It prevents backflow from storage tank to heating boiler.

The function of the backflow preventer can, if needed, be blocked. 
The backflow preventer is then replaced by a plug LKA art.no: 187 
022. See page 9, part 8.

MOUNTING

For a trouble free system the piping work must be done without air 
pockets. If this is not possible the system must be fitted with air vents.
Several boilers have integrated thermostats for pump control. If 
not, a flue gas thermostat must be installed. The circulation pump 
should start at the same time as the firing. The pump should stop 
soon after the fire has gone out to let the remaining hot water in 
the boiler self-circulate to the storage tank.

PIPE DIMENSIONING BETWEEN HEATING BOILER AND STORAGE 
TANK:

• 

LK 810 ThermoMat 2.0 G Eco loading unit with Rp 1” ball valve.  
For heating boilers up to 40 kW ….. DN 25

• 

LK 810 ThermoMat 2.0 G Eco loading unit with 28 mm ball valves. 
For heating boilers up to 40 kW …. CU 28

•  

LK 810 ThermoMat 2.0 G Eco loading unit with Rp 1¼“ ball valves. 
For heating boilers up to 65 kW …. DN 32

    

 1. Heat up phase

 

 The water circulates between boiler and lo-
ading unit while the temperature of the boiler 
is rising. 

    

    2. Loading phase 

 

 The thermostatic element starts to open and 
allows return water from the storage tank to 
be mixed with supply water before it returns 
to the boiler. The return temperature to the 
boiler is kept constant.

    

    3. End phase

 

 The thermostatic element is fully open and 
the bypass is closed. This results in an opti-
mal transfer of heat from the boiler and the 
storage tank is filled with supply water.

    

    4. Self-circulation with check valve

 

 Self-circulation will be obtained as soon as the 
fire has gone out and the circulating pump has 
stopped. The remaining hot water is loaded to the 
storage tank. In case of power failure or pump 
breakdown the check valve automatically opens to 
allow self-circulation. The check valve also stops 
recirculation from storage tank to boiler. 

    

THE FUNCTION OF THE LOADING UNIT DURING THE DIFFERENT 
PHASES OF HEATING: 

Summary of Contents for 810 ThermoMat 2.0 G

Page 1: ...d The backflow preventer is then replaced by a plug LKA art no 187 022 See page 9 part 8 MOUNTING For a trouble free system the piping work must be done without air pockets If this is not possible the system must be fitted with air vents Several boilers have integrated thermostats for pump control If not a flue gas thermostat must be installed The circulation pump should start at the same time as ...

Page 2: ...Mat 2 0 G Eco Ladeventileinheit mit 28 mm Absperrventile Für Kessel bis 40 kW CU 28 LK 810 ThermoMat 2 0 G Eco Ladeventileinheit mit Rp 1 Absperrventile Für Kessel bis 65 kW DN 32 1 Erwärmungsphase Wasser zirkuliert zwischen Kessel und Rück laufanhebung während die Kesseltemperatur steigt 2 Ladephase Der thermische Einsatz öffnet sich und lässt zu dass sich Rücklaufwasser aus dem Pufferspeicher mi...

Page 3: ...hermostat de fumée pour obtenir la fonction rapide arrêt marche DIMENSIONNEMENT Les dimensions de la tuyauterie entre la chaudière et le ballon tampon LK 810 ThermoMat 2 0 G Eco Rp 1 pour chaudière jusqu à 40kW DN 25 LK 810 ThermoMat 2 0 G Eco 28 pour chaudière jusqu à 40 kW CU 28 LK 810 ThermoMat 2 0 G Eco Rp 1 pour chaudière jusqu à 65 kW DN 32 1 Phase de chauffage L eau circule entre la chaudiè...

Page 4: ... di accumulo e contemporaneamente garantire una elevata temperatura di ritorno verso la caldaia Questo aumenta l efficienza del sistema e garantisce una lunga durata della caldaia in quanto riduce la formazione di condensa e catrame CIRCOLATORE Il circolatore può essere regolato su 4 posizioni in modo da modifi care il fl usso in funzione della potenza del generatore É importante considerare che l...

Page 5: ...olla varaajaan Jotta jälkilämpöä voidaan hyödyntää on tärkeää että latauspump pu pysähtyy samalla kun palaminen loppuu 2 Sähkökatkon aikana siirtyy energia vapaakierron avulla varaajaan 3 Takaiskuventtiili estää paluukierron varaajasta kattilaan Takaiskuventtiilin toiminta voidaan tarvittaessa kytkeä pois päältä Takaiskuventtiili vaihdetaan tulppaan LKA tuote nr 187 022 Katso sivu 9 osa 8 PUTKIMIT...

Page 6: ...kiktning i ackumulatortanken och hålla en hög returtemperatur till pannan vilket höjer anläggningens verkningsgrad Tjärbildning och kon dens motverkas vilket ökar pannans livslängd BACKVENTILENS FUNKTION LK 810 ThermoMat 2 0 G ECO laddningspaket har beroende på modell en inbyggd backventil som öppnar automatiskt för självcir kulation när laddningspumpen inte är i drift Självcirkulationen har tre v...

Page 7: ... www lkarmatur de WITH CHECK VALVE WITHOUT CHECK VALVE PUMP CHARACTERISTICS UPM3 AUTO L 0 10 20 30 40 50 60 70 0 0 0 5 1 0 2 0 2 5 3 0 ʉ S N3D 1 5 ORZ Pu K Max I II III BOILER CAPACITY DIAGRAM 0 20 40 60 80 100 0 0 0 5 1 0 2 0 2 5 3 0 DSDFLW N 1 5 ORZ Pu K ...

Page 8: ... 187329 Ball valve with handles Absperrkugelhahn mit Griffen Vanne d arrêt avec poignée Valvola a sfera di sezionamento con maniglia Sulkuventtiili kahvoilla Avstängningsventil med handtag Rp 1 3 187017 Ball valve Absperrkugelhahn Vanne d arrêt Valvola a sfera di sezionamento Sulkuventtiili Unionventil Rp 1 4 187018 Ball valve Absperrkugelhahn Vanne d arrêt Valvola a sfera di sezionamento Sulkuven...

Page 9: ...werden AVERTISSEMENT Ce produit peut être utilisé par des enfants de 8 ans et plus ainsi que par des personnes présentant des troubles physiques sensoriels ou mentaux ou manquant d expérience et de connais sances sur le produit Ces personnes doivent cependant l utiliser sous surveillance ou avoir été formées à l utilisation du produit Elles doivent être en mesure de comprendre les dangers impli qu...

Page 10: ...ENG DE FR IT FI SE 10 www lkarmatur se www lkarmatur com www lkarmatur de 1x230V 10 15 50Hz L N Min 3 mm 1 5 L PE N 6 7 2 3 1 ...

Page 11: ...FORMANCE VIEW ALARM STATUS Blocked Supply voltage low Electrical error 10 s SETTING MENU PERFORMANCE SELECTED SETTING 2 s X 10 s SELECTED SETTING 2 s OPERATION STATUS 10 s SETTING SELECTION SETTING SELECTION KEY LOCK STANDBY 0 P1 25 25 P1 50 50 P1 75 75 P1 100 ONLY PWM CONTROLLED 25 50 75 100 ...

Page 12: ...PM 3 x x 5 0 U PM 3 x x 70 CO N T RO L M O D E M O D E U PM 3 x x 5 0 U PM 3 x x 70 CO N T RO L M O D E M O D E U PM 3 x x 5 0 U PM 3 x x 70 PRE SET PROPORTIONAL PRESSURE CONSTANT PRESSURE PROPORTIONAL PRESSURE CONSTANT PRESSURE PROPORTIONAL PRESSURE CONSTANT PRESSURE 1 1 2 2 3 3 1 1 2 2 3 3 CO N T R O L M O D E M O D E U PM 3 x x 5 0 U PM 3 x x 70 CO N T R O L M O D E M O D E U PM 3 x x 5 0 U PM ...

Page 13: ...ENG DE FR IT FI SE 13 www lkarmatur se www lkarmatur com www lkarmatur de ...

Page 14: ...se Erklärung bezieht mit den folgenden Richtlinien des Rates zur Angleichung der Rechtsvorschriften der EU Mitgliedsstaaten übereinstimmen DÉCLARATION DE CONFORMITÉ CE Nous Grundfos déclarons sous notre seule responsabilité que le produit GFNJB variantes UPM3 avec interface utilisateur et GFNJC autres variantes UPM3 auxquels se réfère cette déclaration sont conformes aux Directives du Conseil conc...

Page 15: ...r se www lkarmatur com www lkarmatur de ON 1 OFF 0 REPLACING THERMOSTATIC ELEMENTS AUSTAUSCH DES THERMOSTATEINSATZES REMPLACEMENT DE LA CARTOUCHE SOSTITUZIONE DELL INSERTO TERMOSTATICO TERMOSTAATIN VAIHTO BYTE AV TERMISK INSATS 2 3 4 1 ...

Page 16: ...LK ARMATUR AB www lkarmatur com LK ARMATUR DEUTSCHLAND GMBH www lkarmatur de Art nr 148873 22 01 ...

Reviews: