background image

1 (9)

Install the electric valves on the hot and cold water 

supply pipes for the relevant room. Installation of 

electric valves must be carried out by a qualified 

plumber in accordance with industry regulations 

for safe water installation. 

NOTE!

Install electric valves after any feed to a 

safety system that requires water.

Safety systems such as home sprinklers or emer-

gency cooling for a solid fuel boiler etc. should be 

connected before the electric valve, to avoid any 

risk to their water supply. An installation with a 

water filter that is backwashed should also be con-

nected before the electric valve to avoid interfering 

with its function. The system prevents water dam-

age that may occur after the electric valve position.

The LK Water Safety System WSS can alternatively 

be mounted in the LK Installation Cabinet on a 

wall or ceiling.

Implementation

The LK Water Safety System WSS is a product 

designed to prevent or limit water damage. The LK 

WSS PIR system is intended to control the water 

supply with motion detection in public environ-

ments such as toilets, showers, changing rooms 

etc. A leak detector can also be fitted where there 

is a risk of leaks. The system is developed to be 

user-friendly and reliable.

System description

The LK Water Safety System WSS PIR consists of a 

master unit, a PIR motion detector and two electric 

valves. Additional motion and leak detectors can 

be added to the system.

When the PIR sensor detects motion, it gives a 

signal to the master unit, which opens the electric 

valves for the water supply. A timer function also 

starts, which shuts off the water supply after a 

preset time when no further motion is detected. 

The PIR sensor is always connected by wire.

One or more leak detectors can be connected by 

wire or wirelessly as accessories. Leak detectors 

can be located where there is a risk of leaks. When 

they detect a leak, the master unit closes the elec-

tric valves, shutting off the water supply. In this 

state, the PIR sensor cannot open the water supply 

until the leak detector and master unit have been 

reset. The leak detector also has a built-in tempera-

ture monitor to shut off the water at temperatures 

under 5° C.

The master unit can also act as a leak detector by 

connecting an LK Sensor WSS.

System assembly

Installing electric valves

LK Water Safety System WSS PIR

EN.40.C.9.1911

Installation guide | LK Water Safety System WSS PIR

 

Summary of Contents for WSS PIR

Page 1: ...s etc A leak detector can also be fitted where there is a risk of leaks The system is developed to be user friendly and reliable System description The LK Water Safety System WSS PIR consists of a master unit a PIR motion detector and two electric valves Additional motion and leak detectors can be added to the system When the PIR sensor detects motion it gives a signal to the master unit which ope...

Page 2: ... per form a pressure test at 1 43 x estimated pressure i e 14 3 bar and inspect all new joints Installing the master unit Position the master unit close to the electric valves The cables are about 0 8 m long and can be extended up to 3 m using the same cable area 2 x 0 5 mm2 Fit the antenna included in the socket on top of the master unit Attach the master unit to the wall using suitable screws in...

Page 3: ...the required number of holes in the rub ber gasket for cable penetration Use the cable ties supplied for strain relief Secure the cable tie in the hole pattern in the black rubber gasket Replace the cover Screw the cover back onto the main unit Ensure the flexible cable is not twisted When all of the units to be connected with bus communication have been connected connect the master unit s network...

Page 4: ...e to D and The cable should be twinned type 2 x 0 5 mm2 D D Terminal on the leak detector for bus communication Place the leak detector at a suitable height from the floor so the sensor cable can reach down to its location The detector should be easy to access for changing batteries and to reset any alarms that are indicated with a sound and diode lights Secure the leak detector with suitable scre...

Page 5: ... seconds to reset the alarm Operating instructions Installing a LK Water Safety System reduces the risk of water damage in a property The system is controlled and monitored by the master unit A leak detector and PIR sensor are connected to the master unit Keys There are three keys on the master unit used for controlling the system When a key is pressed it will light up or flash Water open Open Ind...

Page 6: ...ity In the event of an alarm If an alarm occurs identify which unit it is for and the cause A alarms Reset the leak detector s water alarm by pressing the red key on the underside of the leak detector The sensor may also need to be dried or the alarm will recur Cut off a temperature alarm by pressing the red key on the underside of the leak detector The diode stops flashing when the temperature ri...

Page 7: ...e or the Quick Guide Removing units from the system If removing a unit from the system the system will have to be reset Refer to Resetting the System The relevant units can then be reprogrammed Resetting the system Reset the system to default settings on the master unit as follows 1 Disconnect power to the master unit 2 Press the Timer key 3 Reconnect the power at the same time as hold ing down th...

Page 8: ...very installation should therefore be tested indi vidually Environment LK Systems is affiliated with El Kretsen for collect ing and recycling electronics and batteries Used batteries should be sorted as batteries or small bat teries and deposited for battery recycling When the system has reached the end of its life it should be sorted as electronics or other electronics and deposited with a recycl...

Page 9: ...ensor WSS RSK 188 25 44 LK Sensor with branch cable WSS RSK 188 22 22 LK Branch Cable WSS RSK 188 22 23 LK Extension Cable WSS RSK 188 22 88 LK Bracket WSS Manifold Cabinet UNI RSK 188 22 21 LK Rail WSS Manifold Cabinet UNI RSK 188 23 21 LK Systems AB Box 66 161 26 Bromma Sweden www lksystems se en Installation guide LK Water Safety System WSS PIR EN 40 C 9 1911 ...

Reviews: