background image

7 (9)

In the event of a valve fault alarm, check that the 

white knob is pressed down on the electric valves, 

and that the cable for the cold and hot water valves 

is connected to the correct contact in the master 

unit. If a electric valve for hot water is connected, 

DIP switch no. 6 must be in the ON or OFF posi-

tion. The valve is monitored. Test by opening and 

closing it a few times. Reset an A-alarm by holding 

down the Open or Close key on the master unit 

for 5 seconds.

B-alarms

If a communications alarm is displayed on the 

master unit. Find the unit with a communication 

fault. Bring it closer to the master unit or connect it 

to the master unit using a bus cable. This is shown 

on the leak detector when the right diode flashes

A communication alarm will reset when the unit 

regains contact with the master unit. Press one 

of the keys on the unit to send data to the master 

unit and to check whether the communication is 

working.

A battery alarm can be due to low battery level in 

one of the leak detectors. This is shown when the 

left diode on the leak detector flashes red. Find the 

unit that has low battery and replace the battery.

Following a B-alarm for communication or battery, 

the alarm will automatically reset when commu-

nication is working again or a battery is replaced.

Expanding the system 

To add one or more units to the system, refer to 

Starting the System in this guide, or the Quick 

Guide.

Removing units from the system 

If removing a unit from the system, the system will 

have to be reset. Refer to Resetting the System. The 

relevant units can then be reprogrammed.

Resetting the system. Reset the system to default 

settings on the master unit as follows: 

1. Disconnect power to the master unit. 

2. Press the Timer key. 

3. Reconnect the power at the same time as hold-

ing down the Timer key. The unit will flash during 

reset. Continue to hold down the key until all three 

diodes are on. Reset is now complete. 

Only the master unit needs to be reset. Leak detec-

tors cannot be reset. Once the master unit has been 

reset to default settings, the system can be repro-

grammed according to Starting the System in this 

guide.

Manually opening/closing 

A electric valve can be forced open by lifting and 

turning the white handle (1) until the status indica-

tor (2) indicates the valve is open. Press the handle 

down again. Closing can be achieved in the same 

way. Turn the handle until the status indicator dis-

plays closed.

Valve with status indicator and emergency opening handle.

Operation and maintenance

Check system function after installation and once 

every year. Test leak detectors by moistening the 

sensors.

The unit and master unit will set off a visual and 

audible alarm and the electric valve should shut 

off. Reset the alarm by drying the sensor. Then 

press the red key on the underside of the leak 

detector. Hold the Open or Close key for 5 sec-

onds on the master unit or control panel to reset 

the alarm.

Installation guide | LK Water Safety System WSS PIR

EN.40.C.9.1911

Summary of Contents for WSS PIR

Page 1: ...s etc A leak detector can also be fitted where there is a risk of leaks The system is developed to be user friendly and reliable System description The LK Water Safety System WSS PIR consists of a master unit a PIR motion detector and two electric valves Additional motion and leak detectors can be added to the system When the PIR sensor detects motion it gives a signal to the master unit which ope...

Page 2: ... per form a pressure test at 1 43 x estimated pressure i e 14 3 bar and inspect all new joints Installing the master unit Position the master unit close to the electric valves The cables are about 0 8 m long and can be extended up to 3 m using the same cable area 2 x 0 5 mm2 Fit the antenna included in the socket on top of the master unit Attach the master unit to the wall using suitable screws in...

Page 3: ...the required number of holes in the rub ber gasket for cable penetration Use the cable ties supplied for strain relief Secure the cable tie in the hole pattern in the black rubber gasket Replace the cover Screw the cover back onto the main unit Ensure the flexible cable is not twisted When all of the units to be connected with bus communication have been connected connect the master unit s network...

Page 4: ...e to D and The cable should be twinned type 2 x 0 5 mm2 D D Terminal on the leak detector for bus communication Place the leak detector at a suitable height from the floor so the sensor cable can reach down to its location The detector should be easy to access for changing batteries and to reset any alarms that are indicated with a sound and diode lights Secure the leak detector with suitable scre...

Page 5: ... seconds to reset the alarm Operating instructions Installing a LK Water Safety System reduces the risk of water damage in a property The system is controlled and monitored by the master unit A leak detector and PIR sensor are connected to the master unit Keys There are three keys on the master unit used for controlling the system When a key is pressed it will light up or flash Water open Open Ind...

Page 6: ...ity In the event of an alarm If an alarm occurs identify which unit it is for and the cause A alarms Reset the leak detector s water alarm by pressing the red key on the underside of the leak detector The sensor may also need to be dried or the alarm will recur Cut off a temperature alarm by pressing the red key on the underside of the leak detector The diode stops flashing when the temperature ri...

Page 7: ...e or the Quick Guide Removing units from the system If removing a unit from the system the system will have to be reset Refer to Resetting the System The relevant units can then be reprogrammed Resetting the system Reset the system to default settings on the master unit as follows 1 Disconnect power to the master unit 2 Press the Timer key 3 Reconnect the power at the same time as hold ing down th...

Page 8: ...very installation should therefore be tested indi vidually Environment LK Systems is affiliated with El Kretsen for collect ing and recycling electronics and batteries Used batteries should be sorted as batteries or small bat teries and deposited for battery recycling When the system has reached the end of its life it should be sorted as electronics or other electronics and deposited with a recycl...

Page 9: ...ensor WSS RSK 188 25 44 LK Sensor with branch cable WSS RSK 188 22 22 LK Branch Cable WSS RSK 188 22 23 LK Extension Cable WSS RSK 188 22 88 LK Bracket WSS Manifold Cabinet UNI RSK 188 22 21 LK Rail WSS Manifold Cabinet UNI RSK 188 23 21 LK Systems AB Box 66 161 26 Bromma Sweden www lksystems se en Installation guide LK Water Safety System WSS PIR EN 40 C 9 1911 ...

Reviews: