Note
: Use These Instructions for
ULC Installations
Prerequisites, Specifications and Installation
Options
General prerequisites
The following conditions must be met before installing the LNI 2000:
A completed work order including,
at a minimum
, these settings:
•
Static IP address of LNS;
•
Receiver number;
•
LNS encryption passphrase;
•
Indication whether LNI 2000 will use DHCP or a static IP address,
with DHCP as the default;
•
If static IP address is specified, the address, the subnet mask and
gateway mask; and
•
Password to be used to configure the LNI.
CAN/ULC S559 prerequisites
Compatible CAN/ULC-559-04 listed alarm panel.
Compatible with all Dact/Receivers that use compatible data formats
(see Compatible LoBenn Network Server (LNS) Data Formats)
ULC listed enclosure, such as the GE MFC(A) Accessory Enclosure
installed, with ULC listed mounting plate and ULC listed 12V DC
voltage regulator. Shall use the GE 24DC12 compatible by voltage
range (21 to 26VDc)
ULC listed conduit between alarm panel and enclosure containing the
LNI 2000 with appropriate cabling in place.
Available Ethernet port on a router connected to high-speed modem.
Active POTS telephone line from alarm panel (optional, for
redundancy).
A CAN/ULC S559 compliant 24-hour power supply.
CAN/ULC S304 prerequisites
Compatible CAN/ULC-S304-06 listed alarm panel.
Available Ethernet port on a router connected to high-speed modem.
Router and modem protected by ULC listed enclosure, or inside
burglary alarm panel enclosure.
LNI 2000 Installation Manual
10