Note
: Use These Instructions for
Standard
Installations
Note:
To be ULC CAN/ULC-S559-04 and CAN/ULC S304-06
compatible, the Tamper Switch Enable must be set to use the
Tip/Ring method. This is applicable for panels/dialers such as the GE
Fireshield series which have the following characteristics:
•
There is no dedicated tamper circuit between the panel/dialer and
the LNI
•
The Tip/Ring wires are shorted to the T1/R1 leads respectively
when the dialer is on hook.
Note
: To be ULC compatible tamper protection must be activated.
1.
Enter the primary and secondary LNS IP addresses supplied by monitoring
center. Refer to the work order for this information.
Note:
Only one address needs to be entered. If there are redundant or
defunct addresses the LNS will update the LNI 2000 automatically.
Note:
Consult the monitoring center before adding additional
addresses. Attempts to connect are made in order, using each address
provided. The LNI will use the CTAT value before trying each
address in sequence. Fall-back to the PSTN line will only occur after:
•
CTAT is exceeded and no connection can be made to a backup
LNS; or
•
CTAT is not exceeded, but the alarm panel is attempting to send an
alarm. If at that moment a connection cannot be established, the
LNI will default to the PSTN line.
2.
Enter the LNS encryption phrase in the space provided. LoBenn Inc.
strongly recommends that the passphrase be copied from the license key file
provided by the monitoring center and pasted into this field.
Note:
All communications with the LNI are always encrypted.
Therefore the LNI satisfies ULC CAN/ULC-S304-06 which requires
that the active communication channel must have security encryption
enabled at all times (CAN/ULC-S304-06: 11.4.2.5).
3.
Save these settings by clicking “Submit.”
4.
To change the LNI 2000 password, click on Change Password on the upper
right hand corner of the LoBenn LNI Configuration
screen.
LNI 2000 Installation Manual
36