For All Installations
UL Compliance
For the equipment an its installation to comply with the applicable UL
requirements (UL 864 and UL 1610), this product
MUST
be installed in a UL
certified Signal Receiving Centre that provides this product with standby supply
from both of the following sources.
1. A standby generator that complies with the applicable UL requirements
associated with a Signal Receiving Centre, AND
2. An uninterruptible power supply (UPS) that is capable of maintaining
operation for 4 hours and that is listed to the applicable UL
requirements.
UL 864 and UL 1610
This equipment is UL listed to UL 864 and UL 1610.
Communications Basic Line Security
This product meets the requirement for communication basic line security level.
Other UL Compliance Requirements
Receiver
To be UL 864 and UL 1610 compatible, the system must be used with a listed
receiver.
Network and Domain Access
To be UL 1610 compatible, network access and domain access policies shall be
set to restrict unauthorized network access and “spoofing” or “denial of service”
attacks.
Encryption
All communications with the LNI and LNS are always encrypted. Therefore the
LNI and the LNS satisfy UL 1610 which requires that the active communication
channel must have security encryption enabled at all times.
LoBenn Network Interface 2000 Installation Manual
72