IGNITION STATE AND TIMING
IGNITION STATE
TIMING
Pre-purge
5 seconds (NG models)
15 seconds (LP models)
Hot Surface Igniter
(HSI) Warmup
10 seconds
Ignition Activation
Period (IAP)
3.5 seconds maximum
Flame Recognition
Period (FRP)
0.5 second
Trial For Ignition
IAP + FRP
Flame Stabilization
Period
Not Applicable
Inter-purge
30 seconds
Flame Failure
Response Time
2 seconds max
(@ 1uA flame current)
Post-purge
30 seconds
Pressure Switch (PS)
Prove Period
2 minutes
Pressure Switch (PS)
Fault Delay (failed
open/closed)
2 minutes
Soft Lockout
20 minutes
Energy Cut Off
(ECO) Limit Lockout
Indefinite
Flammable Vapor
(FV) Sensor Lockout
Indefinite (see
“Resetting The Heater Control”)
SYSTEM STATUS AND ERROR CODES
The micro-controller inside the gas control monitors the
flammable vapor safety features, the ignition sequence,
temperature settings and overall operation of the heater.
If any of these parameters does not operate properly the
controller will shut down the water heater, diagnose the
failure and flash an error code. The table below lists the
System Status Codes for the Honeywell control. Refer
to it and to the “Troubleshooting Guidelines” to diagnose
the problem before attempting corrective action. See also
“Flammable Vapor Sensor”.
LED Flash
Sequence
Control Status
Short flash
once every four
seconds
IDLE (no call for heat,
no fault conditions)
“Heartbeat”,
alternates bright/dim
Call For Heat
(no fault conditions)
One Flash,
three second pause
Low Flame Signal
(control continues to operate)
Two Flash,
three second pause
Pressure Switch Failed
Closed
Three Flash,
three second pause
Pressure Switch Failed Open
Four Flash,
three second pause
ECO (Energy Cut Off) Limit
Lockout
thermostat temperature limit
was exceeded.
Five Flash,
three second pause
Flame Out Of Sequence
Six-One Flash,
three second pause
Soft Lockout
- Retry Limit
- Failed Trial For Ignition
Six-Two Flash,
three second pause
Soft Lockout
- Recycle Limit
- Pressure Switch/High Limit
opened
Six-Three Flash,
three second pause
Soft Lockout
- Recycle Limit
- Flame Lost
Six-Four Flash, three
second pause
Soft Lockout
- Flame out of Sequence
Sensed
Seven Flash,
three second pause
Flammable Vapor Sensor
(FVS) Lockout
Eight-One Flash,
three second pause
Flammable Vapor Sensor
FVS Fault Detected
Eight-Two Flash,
three second pause
Temperature Sensor Fault
Detected
Eight-Three Flash,
three second pause
Electronics Fault Detected
Eight-Four Flash,
three second pause
Valve Fault Detected
Hardware Fault
Lockout
Indefinite