FLUE SYSTEM TECHNICAL DETAILS AND MAXIMUM FLUE LENGTH
Model Number
EKW46CE
EKW61CE
EKW86CE
FLUE DATA TYPE B
23
Nominal flue diameter
mm
80+/-0.6
100+/-0.6
Maximum flue gas temp
°C
120
Maximum equivalent length
m
60
Equivalent length 90
bend
mm
1000
Equivalent length 45
bend
mm
500
Flue gas temperature
°C
70
Flue draught requirements
mbar
-0.03 to -0.1
FLUE DATA TYPE C
13
& C
33
Nominal flue diameter
mm
80/125
100/150
Maximum flue gas temp
°C
120
Maximum equivalent length
m
30
Equivalent length 90
bend
mm
1000
Equivalent length 45
bend
mm
500
FLUE DATA TYPE C
43
& C
53
Nominal flue diameter
mm
80
100
Average flue gas temp (80/60 Flow/Return)
°C
70
Maximum flue gas temp
°C
120
Maximum equivalent length
m
60*
Equivalent length 90
bend
mm
1000
Equivalent length 45
bend
mm
500
10.2.1
FLUE
SYSTEM
TECHNICAL
DATA
TABLE
*
On twin pipe systems, the maximum equivalent length is the sum of the air inlet components and the exhaust
components.
10.3
FLUE DISCHARGE
The flue system must ensure safe and efficient operation of the equipment to which it is attached, protect the combustion process
from wind effects and disperse the products of combustion to open external air.
The flue must terminate in a freely exposed position and be so situated as to prevent the products of combustion entering any
opening in a building. For installations with a total output above 200kW, the clean air act should be consulted and complied with.
Under certain operating and weather conditions, the EcoKnight™ water heater may generate a plume at the terminal. Consideration
should be given to the nuisance this may cause and the terminal should be sited accordingly.
For further information on terminal locations, please refer to Section 10.4.1 FLUE TERMINAL POSITIONS.
10.4
CONDENSATE DRAIN
If the flue system rises at an angle of at least 3
(50mm per metre), no additional condensate drain will be required. Failure to
provide an adequate rise in the flue system may lead to pooling of condensate which may lead to premature failure of the flue system.
Summary of Contents for ECOKNIGHT EKW116CE
Page 28: ...28 Max distance between brackets ...
Page 29: ...29 ...
Page 30: ...30 ...
Page 34: ...34 ...
Page 35: ...35 ...
Page 55: ...55 15 8 WIRING DIAGRAM 15 8 1 WIRING DIAGRAM ...
Page 56: ...56 15 9 LADDER DIAGRAM 15 9 1 LADDER DIAGRAM ...
Page 87: ...87 ...
Page 88: ...88 ...