59
6
If flame is not detected after spark ends the control will perform a post-purge, then
start another pre-purge cycle and try to light the water heater again. On the 145
model up the control will lock out after this second attempt on the 115 down a
further four attempts will be made before the unit goes to lock-out.
7
If the flame is detected it holds the firing rate steady for a few seconds then begins
to modulate the firing rate based on a set point or some other command (such as
the 0-10v signal)
8
Once the call for heat is satisfied the control will turn off the burner. The fan will
continue to run during the post-purge period.
9
Any pumps that are running will continue for their respective pump overrun time
period before switching off. A 60 second anti-cycle period will start which will delay
any call for heat.
10
In standby ready to start a new cycle.
1.1.1
SEQUENCE
OF
OPERATION