83
23.4
SMART SYSTEM CONTROL
1 USB Drive
2 PC Connection
3 Left select key
4 Navigation dial
5 Reset switch
6 Right select key
The information on the bottom of the display shows the functions of the two SELECT keys on both corner, and the NAVIGATION
dial in the centre.
MENU
Left SELECT key
SETPOINTS
NAVIGATION dial-pressing down
SHDN
Right SELECT key
The smart system control face instantly informs the user of the status of the Water Heater by changing colour according to the status
of the Water Heater as below.
Normal operation
Service required
Water Heater is not working
23.5
TEMPERATURE ADJUSTMENT PROCEDURE
23.5.1
DHW
SETPOINT
The stored water temperature is controlled by a tank sensor supplied with the water heater, the default setpoint is 52
C.
The setpoint should be adjusted to ensure that the water is stored at 60°C and distributed at 50°C within 1 (one) minute at all outlets.
Care is needed to avoid much higher temperatures because of the risk of scalding. At 50°C the risk of scalding is small for most
people, but the risk increases rapidly with higher temperatures and for longer exposure times. The risk to young children and to
those with a sensory or mobility loss will be greater. Where a significant scalding risk has been identified, the use of thermostatic
mixing valves on baths and showers should be considered to reduce temperature, this need to be placed as close to the point of use
as possible.
Should the default value need adjusting, please refer to Section 17.5 Temperature adjustment
1
2
3
4
6
5
Summary of Contents for ECOKNIGHT EKW116CE
Page 28: ...28 Max distance between brackets ...
Page 29: ...29 ...
Page 30: ...30 ...
Page 34: ...34 ...
Page 35: ...35 ...
Page 55: ...55 15 8 WIRING DIAGRAM 15 8 1 WIRING DIAGRAM ...
Page 56: ...56 15 9 LADDER DIAGRAM 15 9 1 LADDER DIAGRAM ...
Page 87: ...87 ...