52
15.3
HIGH VOLTAGE CONNECTOR STRIP
15.3.1
HIGH
VOLTAGE
CONNECTION
STRIP
The output across the 3 terminals should not exceed 190W per terminal.
It is highly recommended these switched outputs are only used to switch suitable
starter/overload relays on the pumps.
CONNECTION
OUTPUT
NOTES
PRIMARY
230VAC – Output is when there is a call for DHW
MAX 190 WATTS
230 VAC Live, Neutral and Earth connections for a primary
circulation pump starter.
NOTE: On all EcoKnight™ water heaters, the primary pump
exceeds the maximum power output and therefore a suitable
starter/overload relay will be required.
DE-STRAT
NO OUTPUT
CONNECTION NOT USED
RETURN
230VAC – Constant output when unit powered
MAX 190 WATTS
230 VAC Live, Neutral and Earth connections for a secondary
circulation pump. If the pump rating exceeds the maximum 190
watts available over the three terminals, the Live and Neutral
connections should then be used to switch a suitable
starter/overload relay.
MAINS
Connections for a 230V ~ 1 ph 50Hz power supply. NOTE: The
power supply cable should be secured using the anchor supplied.
15.3.2
HIGH
VOLTAGE
CONNECTION
TERMINAL
DETAILS
15.4
LOW VOLTAGE CONNECTOR STRIP
The low voltage connector strip is used on both EcoKnight water heaters and Herald boilers; as
such, some connections will not be applicable to your installation.
15.4.1
LOW
VOLTAGE
CONNECTION
STRIP
Summary of Contents for ECOKNIGHT EKW116CE
Page 28: ...28 Max distance between brackets ...
Page 29: ...29 ...
Page 30: ...30 ...
Page 34: ...34 ...
Page 35: ...35 ...
Page 55: ...55 15 8 WIRING DIAGRAM 15 8 1 WIRING DIAGRAM ...
Page 56: ...56 15 9 LADDER DIAGRAM 15 9 1 LADDER DIAGRAM ...
Page 87: ...87 ...
Page 88: ...88 ...