24
9.0
AIR SUPPLY
The following information is based on single water heater installations only. If more than one water heater is being
used
BS6644
should be consulted to calculate the necessary requirements.
9.1
COMBUSTION VENTILATION
When used as a Type C appliance, provided sufficient clearance is provided, ventilation for combustion is not
necessary as the combustion air is ducted directly from outside.
When used as a Type B appliance, the combustion air requirements are as follows:
Model
Gross
Input
(kW)
Net
Input
(kW)
Ventilation
(Room)
(cm
2
)
Compartment
Compartment
(Direct to Outside)
(To Internal Space)
High
(cm
2
)
Low
(cm
2
)
High
(cm
2
)
Low
(cm
2
)
EKW45CE
43.9
39.6
165
200
400
400
800
EKW60CE
58.6
52.8
230
265
530
530
1060
TABLE 9.1
COMBUSTION VENTILATION REQUIREMENTS EKW45CE – EKW60CE
Model
Gross
Input
(kW)
Net
Input
(kW)
Plant Room
Enclosure
Low
Summer Use
Medium
Summer Use
High
Summer Use
Low
Summer Use
Medium
Summer Use
High
Summer Use
High
(cm
2
)
Low
(cm
2
)
High
(cm
2
)
Low
(cm
2
)
High
(cm
2
)
Low
(cm
2
)
High
(cm
2
)
Low
(cm
2
)
High
(cm
2
)
Low
(cm
2
)
High
(cm
2
)
Low
(cm
2
)
EKW85CE
83.5
75.3
152
304
228
380
304
456
380
760
456
836
532
912
EKW115CE
117.2 105.6
212
424
318
530
424
636
530
1060
636
1166
742
1272
EKW145CE
146.5 132.0
264
528
396
660
528
792
660
1320
792
1452
924
1584
EKW175CE
175.8 158.4
318
636
477
795
636
954
795
1590
954
1749
1113
1908
EKW205CE
205.2 184.5
370
740
555
925
740
1110
925
1850
1110
2035
1295
2220
EKW235CE
234.5 211.3
424
848
636
1060
848
1272
1060
2120
1272
2332
1484
2544
TABLE 9.2
COMBUSTION VENTILATION REQUIREMENTS EKW85CE – EKW145CE
9.2
COOLING VENTILATION
When used as a type C appliance, installed in a compartment or an enclosure, as shown in
Figure 3.1
, cooling
ventilation should be provided as follows:
Model
Input
(Gross)
kW
Input
(Net)
kW
Enclosure/Compartment
Enclosure/Compartment
Boiler Room
(Direct to Outside)
(To Internal Space)
High
(cm
2
)
Low
(cm
2
)
High
(cm
2
)
Low
(cm
2
)
High
(cm
2
)
Low
(cm
2
)
EKW45CE
43.9
39.6
200
200
400
400
N/A
N/A
EKW60CE
58.6
52.8
265
265
530
530
N/A
N/A
EKW85CE
83.5
75.3
380
380
760
760
152
152
EKW115CE
117.2
105.6
530
530
1060
1060
212
212
EKW145CE
146.5
132.0
660
660
1320
1320
264
264
EKW175CE
175.8
158.4
795
795
1590
1590
318
318
EKW205CE
205.2
184.5
925
925
1850
1850
370
370
EKW235CE
234.5
211.3
1060
1060
2120
2120
424
424
TABLE 9.3
COOLING VENTILATION REQUIREMENTS
When used as a type B appliance, provision for cooling ventilation is included in the combustion ventilation allowance.