11.2
HIGH VOLTAGE CONNECTOR STRIP
FIGURE 11.1
HIGH VOLTAGE CONNECTION STRIP
CONNECTION
NOTES
PRIMARY
230 VAC Live, Neutral and Earth connections for a primary circulation pump starter.
NOTE:
On all EcoKnight™ water heaters, the primary pump exceeds the maximum power output and therefore a
suitable pump starter will be required.
DE-STRAT
230 VAC Live, Neutral and Earth connections for a system de-stratification pump. If the pump rating exceeds 190
watts, the Live and Neutral connections should be used to energise a suitable contactor.
RETURN
230 VAC Live, Neutral and Earth connections for a building return pump. If the pump rating exceeds 190 watts,
the Live and Neutral connections should be used to energise a suitable contactor.
MAINS
Connections for a 230V ~ 1 ph 50Hz power supply.
NOTE:
the power supply cable should be secured using the
anchor supplied or an equivalent.
TABLE 11.2
HIGH VOLTAGE CONNECTION TERMINAL DETAILS
11.3
LOW VOLTAGE CONNECTOR STRIP
AUX. DEVICE
PILOT SUPPLY
24VAC
GND
AUX. DEVICE
PROVING
GAS PRESSURE
SWITCH
FLOW
SWITCH
ALARM
CONTACTS
RUNTIME
CONTACTS
TANK
SENSOR
SHIELD GROUND
0-10VDC EXTERNAL
GND CONTROL
TANK THERMOSTAT
A
B
SHIELD GROUND
SEQUENCING
L
OW
W
ATER
C
UTOFF
CN1
CN2
CN3
CN4
CN5
9
10
11
12
13
14
15
16
17
18
19
20
15
21
22
1
2
3
4
5
6
7
8
FIGURE 11.2
LOW VOLTAGE CONNECTION STRIP
PRIMARY
DE-STRAT
RETURN
PUMP OUTPUTS 190 WATTS MAX
230V~50Hz
MAINS
L
N
L
N
L
N
LBL2313 REV B