45
14.2.5
EKW175CE – EKW235CE
1.
Remove the top and front access covers from the unit (no tools required for removal).
2.
Remove the four screws and nuts that hold the adaptor flange to the inlet of the venturi.
3.
Separate the flange and venturi ensuring the gasket is not damaged.
4.
Locate the propane orifice disk from the conversion kit bag. Verify that the stamping on the orifice disk is
correct for the heater (see
Table 14.1
).
5.
Fit the orifice plate ensuring its correct orientation (see DETAIL A of
Figure 14.5
)
6.
Reinstall the four screws and nuts holding the adapter flange to the inlet of the venturi ensuring the correct
location of the gasket.
7.
After installation is complete, attach the propane conversion label (in the conversion kit bag) next to the
heater rating plate.
Attach the LPG warning label (in the conversion kit bag) to the appliance casing, next to
the gas inlet pipework.
8.
Replace the top and front access covers.
FIGURE 14.5
CONVERSION PROCEDURE EKW175CE – EKW235CE