10 

3.3.3

 

TIME & DATE 

 

The control uses an internal clock for the night setback feature and for logging of events.  For these features to 

work correctly, the clock must be set when the water heater is first installed or anytime the water heater has been 

powered off for more than 30 days. 

 

The date and time are displayed as “YY:MM:DD W hh:mm”.  

 

 

YY = year

 

 

MM = month

 

 

DD = date

 

 

W = day (1 = Sunday, 2 = Monday, etc.)

 

 

hh = hour (24 hour time; 2:00 PM = 14:00)

 

 

mm = minutes.

 

 

The date and time are set using the UpDownPrevious and Next buttons.  Once set, the Enter/Reset button 

should be pressed to save the setting. 

 

NOTE:  The clock does not automatically adjust for Daylight Saving Times and therefore will require a manual 

adjustment. 

 

3.3.4

 

SOFTWARE VERSION 

 

This is a display only parameter that will display the version number of the software loaded into the unit. 

 

3.3.5

 

TEMPERATURE UNITS 

 

The control can be configured to display the temperature units in 

°

C of 

°

F.  The default setting is 

°

C, to change 

this, the Up or Down button should be used and the Enter/Reset button pressed to store the desired setting. 

 

3.3.6

 

NIGHT SETBACK TEMPERATURE 

 

Once the internal clock has been set correctly, the night setback feature can be used to program a lower water 

temperature set point for water heating.  This feature is only used when a tank sensor is used.  The temperature 

range for this parameter is 0

°

C to 60

°

c.  The feature is turned off with a setting of 0

°

C.  The default value is 0

°

C.  

To modify the temperature setting, the 

Up or Down button should be used and the Enter/Reset button pressed to 

store the desired setting. 

 

3.3.7

 

NIGHT SETBACK TIME 

 

If the Night Setback Temperature is set to anything other than 0

°

C, the night setback feature becomes active.  

This will require start and stop times to be programmed for the days that reduced temperatures are required.  

Each day of the week (Sunday through Saturday) will have an on and off time.  Using the Previous and Next 

buttons the desired time slot (e.g. Monday ON, Monday Off, Tuesday On etc.) can be selected.  Once the desired 

time slot is selected, the Up and Down buttons can be used to set the required time. 

 

Example: Monday ON: 22:30, Tuesday OFF: 6:45.  If you wish to skip a day and have no night setback, leave the 

on and off times the same.  The default times for each day will be 00:00 (midnight). 

 

 

 

Summary of Contents for EcoShield SHW115-435CE

Page 1: ...he EcoShield range High Efficiency Gas Fired Condensing Water Heaters User SMART SYSTEM Control Guide INS0014 Issue No 1 October 2010 SHW45 325CE SHW60 325CE SHW85 435CE SHW115 435CE SHW145 435CE Models ...

Page 2: ...2 ...

Page 3: ...NTERFACE PANEL 6 2 3 SEQUENCE OF OPERATION 7 2 4 STATUS DISPLAY SCREENS 8 3 0 USER SETTINGS 9 3 1 GENERAL 9 3 2 ENTERING THE USER CODE 9 3 3 MENU SET A GENERAL SETTINGS 9 3 3 1 WATER HEATER MODEL 9 3 3 2 USER CODE 9 3 3 3 TIME DATE 10 3 3 4 SOFTWARE VERSION 10 3 3 5 TEMPERATURE UNITS 10 3 3 6 NIGHT SETBACK TEMPERATURE 10 3 3 7 NIGHT SETBACK TIME 10 3 4 MENU SET C DATA LOGGING 11 3 4 1 TOTAL HRS RU...

Page 4: ... PROCEDURE FOR SHUTTING DOWN To take the appliance out of service the Enter Reset button should be pressed If the appliance in to be shut down for a long period of time the power supply should be isolated using the rocker switch on the back and the gas supply should be isolated at the gas inlet appliance isolating valve 1 4 TEMPERATURE ADJUSTMENT PROCEDURE The setpoint can be adjusted using the Up...

Page 5: ...UPPLY When installed as a conventionally flued appliance the room in which the appliance is installed must be ventilated Blocking these air vents may lead to severe injury serious property damage or death The area in which the appliance is installed should not be used to store any other materials 1 8 CONDENSATE DRAIN The condensate drain must not be blocked or modified in any way If fitted with a ...

Page 6: ...ROL 2 1 GENERAL The Lochinvar EcoShield user control interface gives information on set up system status and diagnostic data in words rather than codes 2 2 USER CONTROL INTERFACE PANEL FIGURE 2 1 USER CONTROL INTERFACE PANEL ...

Page 7: ...cycle is complete and the blocked drain and auto reset high limit are closed the control starts the 5 second trial for ignition by sending spark voltage to the spark electrode and opening the gas valve WHR IGNITION OUT 61 5C 5 If the control does not detect flame by the end of the trial for ignition the control performs a 10 second postpurge On the SHW45 325CE to SHW115 435CE models the control wi...

Page 8: ...ol does not detect the flue sensor SHORTED The flue sensor wires or the sensor itself has become grounded TANK C The control will display the stored water temperature the set point appears in brackets OPEN The control does not detect the tank sensor SHORTED The tank sensor wires or the sensor itself has become shorted Press the Next arrow key on the user control interface panel to access Screen 4 ...

Page 9: ... 7 times The display should now show Enter Menu Code 0704 6 Press the Enter Reset button The display should now show Enter Menu Code USER CODE 3 3 MENU SET A GENERAL SETTINGS After 2 seconds the screen will show A General B N A Pressing the Enter Reset button will access the General menu set From here the following sub sections can be accessed by moving the caret symbol to the appropriate line usi...

Page 10: ...tore the desired setting 3 3 6 NIGHT SETBACK TEMPERATURE Once the internal clock has been set correctly the night setback feature can be used to program a lower water temperature set point for water heating This feature is only used when a tank sensor is used The temperature range for this parameter is 0 C to 60 c The feature is turned off with a setting of 0 C The default value is 0 C To modify t...

Page 11: ...ON ATTEMPTS The Ignition Attempts option will show the number of times the water heater has attempted to fire since the counter was last reset 3 4 3 LAST 10 ERRORS The Last 10 Errors option will show the date time and fault description for the last ten errors that caused the boiler the stop The Up or Down button should be used to scroll through the errors 3 5 EXITING USER SETTINGS MODE To exit the...