61
REPLACING
THE
HEAT
EXCHANGER
If correct water softening precautions are not taken the heat exchanger could become blocked or even split due to scale build up within the heat
exchanger, if this happens the heat exchanger will need to be replaced. Replacement assemblies are available and include all spares required
to replace the heat exchanger. Lochinvar can provide a quote to carry out the replacement work if required.
Replacement heat exchanger assembly item numbers are shown below contact Lochinvar customer service for prices and availability
Heat exchanger replacement assemblies
Model
Item number
SHW35-245
LL200030P
SHW46-325
LL200031P
SHW61-325
LL200032P
SHW86-410
LL200033P
SHW116-410
LL200034P
SHW146-410
LL200035P
18.0
USER CONTROL INTERFACE SETTINGS
18.1
TIME AND DATE
The control uses an internal clock for the night setback feature and for logging of events. For these features to work correctly, the clock must be
set when the water heater is first installed or anytime the water heater has been powered off for more than 15 minutes.
Note that hours are displayed as 24 hour time (2:00PM = 14:00).
Days are displayed as a number (Monday =1, Tuesday = 2, Sunday = 7).
The internal clock does not adjust for British summer time and therefore, will require a manual
adjustment.
18.2
USER ADJUSTABLE PARAMETERS SCREEN
To access the User Adjustable Parameters screen press and hold the ENTER button for 5 seconds. Once pressed the user code u01 should
be shown in the lower digits. There are seven parameters that can be set. Use the UP and DOWN buttons to scroll and the ENTER button to
make selection. Once you have cycled through all of the parameters, the new values will be set.
16.1.1 CODE u01
Temperature units (°C/°F) – Press UP or DOWN to display the desired temperature unit and then press ENTER to make selection.
16.1.2 CODE u02
Hot Water Set Point – The factory default setting is 52°C. The target temperature can be set between 16°C and 85°C. Press UP or DOWN to
display the desired temperature and then press ENTER to make selection.
16.1.3 CODE u03
Year – Press UP or DOWN to display the current year and then press ENTER to make selection.
16.1.4 CODE u04
Month – Press UP or DOWN to display the current month and then press ENTER to make selection.
16.1.5 CODE u05
Day – Press UP or DOWN to display the current day and then press ENTER to make selection.
16.1.6 CODE u06
Hour – Hours are displayed as 24 hour format. UP or DOWN to display the current hour and then press ENTER to make selection.
16.1.7 CODE u07
Minute – Press UP or DOWN to display the current minute and then press ENTER to make selection.