67
19.3
ERROR CODES
The user interface screen gives information on Error codes; these can be one of three types:
1.
Lockout codes, this may require a user reset and/or investigation by a service engineer
2.
Blocking codes, this may require investigation by a service engineer
3.
Notification codes, the unit will continue to operate but a service engineer will be required
Error Codes
Description
Corrective Action
E00
Invalid lockout
Reset control module
Switch power on /off
Replace control module
E01
Memory lockout
Replace control module
E02
Fan speed fault
Check flue and air intake length is not too long
Check for obstruction or blockages within flue system
Check wiring connections on fan and main control board
Replace the fan
Replace the main control board
Blown fuse
Replace Fuse F2 on main control board see
E04
Flow switch fault
Check pump operates on call for heat
Check for closed valves or obstructions
Check system full
Blown fuse
Replace fuse F3 on main control board see
E05
Flame out of sequence
Verify flame not present, if present replace gas valve
Check 230v supply polarity is correct
Check external wiring for voltage feedback
Check flame rod is clean
Check internal wiring for poor connections
Replace main control board
E06
Auto reset Hi limit
Check sensor setting is correct
Check appliance has been filled correctly
Check primary pump operation
Check sensor resistance correct see table
E07
Thermal Fuse open
Check wiring connections to the fuse on the heat exchanger
Check continuity if open contact Lochinvar ltd
E08
Ancillary proving switch
Check ancillary operating correctly
Check wiring to switch
E09
Blocked condense drain
Check for blockages in condense trap/pipework
Check wiring and switch
E10
Air pressure switch/HEX Limit-contacts
are open
Check wiring connections to switch
Check for blockage in air inlet
Check hoses to switch for blockages
Inspect burner and clean/replace as necessary
Inspect heat exchanger clean as necessary
Faulty air pressure switch, replace
Continued over page
Summary of Contents for EcoShield SHW116-410CE
Page 2: ...2 ...
Page 9: ...9 EXPLODED VIEW DRAWINGS ...
Page 27: ...27 Max distance between brackets ...
Page 28: ...28 ...
Page 29: ...29 ...
Page 34: ...34 ...
Page 47: ...47 13 9 LADDER DIAGRAM LADDER DIAGRAM ...
Page 71: ...71 NOTES ...
Page 72: ...72 N ...