USER GUIDE 

 

1.1

 

GENERAL REQUIREMENTS 

 

 

This  equipment  must  be  installed  by  a  competent  person,  registered  with  a  H.S.E.  approved 
body.  All installations must conform to the relevant Gas Safety and Building regulations.  Health 
& safety requirements must also be taken into account when installing any equipment.  

 

 

A competent person must also undertake any alterations that require the gas train or flue system 
to be broken. 

 

 

Any interference with a sealed component is forbidden. 

 

 

Failure to comply with the above may lead to prosecution.

 

 

 

Incorrect use may result in injury and will also invalidate the warranty

 

 

1.2

 

PROCEDURE FOR LIGHTING 

 

1.

 

Ensure that the gas inlet appliance isolating valve is in the “off” position. 

2.

 

Press the power rocker switch, positioned on the back of the appliance to bring the equipment on. 

3.

 

Press the Enter/Reset button on the Smart System control panel to initiate the burner. 

4.

 

The combustion fan should ramp up to full speed to purge the combustion chamber and then drop back 

to half rate in order to light.  As the gas inlet appliance isolating valve is closed, the controls should go to 
a flame failure condition after four ignition attempts (EKW45CE  – EKW115CE) or one ignition attempt 
(EKW145CE – EKW235CE).  If the above occurs correctly, open the gas inlet appliance isolating valve 

and reset the unit by depressing the Enter/Reset button on the control panel. 

5.

 

The  combustion  fan  will  repeat  the  pre-purge  procedure  and  attempt  to  light.    Once  a  flame  is 

established, the LCD display will change to display the rate at which it is firing.  

 

1.3

 

PROCEDURE FOR SHUTTING DOWN 

 
To take the appliance out of service, the 

Enter/Reset

 button should be pressed.  If the appliance in to be shut 

down for a long period of time, the power supply should be isolated using the rocker switch on the back and the 

gas supply should be isolated at the gas inlet appliance isolating valve. 
 

1.4

 

TEMPERATURE ADJUSTMENT PROCEDURE 

 
The  setpoint  can  be  adjusted  using  the  Up  and  Down  buttons  on  the  Smart  System  control  panel.    Once  the 

desired setpoint is displayed, the Enter/Reset button should be pressed to store the value. 
 

The setpoint should be adjusted to ensure that the water is stored at 60°C and distributed at 50°C within 1 (one) 
minute at all outlets.  Care is needed to avoid much higher temperatures because of the risk of scalding.  At 50°C 
the risk of scalding is small for most people, but the risk increases rapidly with higher temperatures and for longer 

exposure times.  The risk to young children and to those with a sensory or mobility loss will be greater.  Where a 
significant scalding risk has been identified, the use of thermostatic mixing valves on baths and showers should be 
considered to reduce temperature, these need to be placed as close to the point of use as possible. 

 

1.5

 

MAINTENANCE 

 
The SMART SYSTEM control has a built in timer that counts the time period, operating hours and burner initiation 
cycles since the unit was last maintained.  Once one of these preset values has been exceeded, the display will 
show 

SERVICE  DUE

  every  5  seconds.    At  this  point,  it  is  strongly  recommended  that  a  competent  person, 

preferably appointed by Lochinvar Limited, carries out the necessary maintenance work. 
 
Details  of  the  necessary  maintenance  work  can  be  found  in  the  Installation,  Commissioning  and  Maintenance 

Instructions. 
 
 

 

Summary of Contents for EKW115CE

Page 1: ...EcoKnight range High Efficiency Gas Fired Condensing Water Heaters User SMART SYSTEM Control Guide Models EKW45CE EKW60CE EKW85CE EKW115CE EKW145CE EKW175CE EKW205CE EKW235CE INS0012 Issue No 5 August 2011 ...

Page 2: ...CONTROL PANEL 5 2 3 SEQUENCE OF OPERATION 6 2 4 STATUS DISPLAY SCREENS 7 3 0 USER SETTINGS 9 3 1 GENERAL 9 3 2 ENTERING THE USER CODE 9 3 3 MENU SET A GENERAL SETTINGS 9 3 3 1 WATER HEATER MODEL 9 3 3 2 USER CODE 9 3 3 3 TIME DATE 10 3 3 4 SOFTWARE VERSION 10 3 3 5 TEMPERATURE UNITS 10 3 3 6 NIGHT SETBACK TEMPERATURE 10 3 3 7 NIGHT SETBACK TIME 10 3 4 MENU SET C DATA LOGGING 11 3 4 1 TOTAL HRS RUN...

Page 3: ...ROCEDURE FOR SHUTTING DOWN To take the appliance out of service the Enter Reset button should be pressed If the appliance in to be shut down for a long period of time the power supply should be isolated using the rocker switch on the back and the gas supply should be isolated at the gas inlet appliance isolating valve 1 4 TEMPERATURE ADJUSTMENT PROCEDURE The setpoint can be adjusted using the Up a...

Page 4: ...UPPLY When installed as a conventionally flued appliance the room in which the appliance is installed must be ventilated Blocking these air vents may lead to severe injury serious property damage or death The area in which the appliance is installed should not be used to store any other materials 1 8 CONDENSATE DRAIN The condensate drain must not be blocked or modified in any way If fitted with a ...

Page 5: ...ROL 2 1 GENERAL The Lochinvar EcoKnight uses the SMART SYSTEM control interface The control panel display gives information on set up system status and diagnostic data in words rather than codes 2 2 SMART SYSTEM CONTROL PANEL ...

Page 6: ...cle is complete and the blocked drain and auto reset high limit are closed the control starts the 5 second trial for ignition by sending spark voltage to the spark electrode and opening the gas valve WHR IGNITION OUT 61 5C 65 5 If the control does not detect flame by the end of the trial for ignition the control performs a 10 second postpurge On the EKW45CE to EKW115CE models the control will perf...

Page 7: ... the unit to fire at 100 of rate for the purpose of combustion analysis OUT C The outlet temperature is displayed OPEN The control does not detect the outlet sensor SHORTED The outlet sensor wires or the sensor itself has become shorted Press the Next arrow key on the SMART SYSTEM display to access Screen 2 2 IN C If a tank sensor is installed only the inlet temperature will be displayed C When a ...

Page 8: ... a tank sensor Cas No Members The Master control could not detect any Member controls to participate in the Cascade PMP Off The Master control has not received a call for heat from a tank sensor and has not powered the primary pump PMP On The Master control has received a call for heat from a remote thermostat and has powered the system pump PMP Delay The tank call for heat has been satisfied and ...

Page 9: ... 7 times The display should now show Enter Menu Code 0704 6 Press the Enter Reset button The display should now show Enter Menu Code USER CODE 3 3 MENU SET A GENERAL SETTINGS After 2 seconds the screen will show A General B N A Pressing the Enter Reset button will access the General menu set From here the following sub sections can be accessed by moving the caret symbol to the appropriate line usi...

Page 10: ...tore the desired setting 3 3 6 NIGHT SETBACK TEMPERATURE Once the internal clock has been set correctly the night setback feature can be used to program a lower water temperature set point for water heating This feature is only used when a tank sensor is used The temperature range for this parameter is 0 C to 60 c The feature is turned off with a setting of 0 C The default value is 0 C To modify t...

Page 11: ... setpoint of the water heater to be adjusted when a flow temperature sensor is not used Lochinvar Limited recommends that a flow sensor is always used with this appliance The setpoint should be adjusted to ensure that the water is stored at 60 C and distributed at 50 C within 1 one minute at all outlets Care is needed to avoid much higher temperatures because of the risk of scalding At 50 C the ri...

Page 12: ......

Reviews: