9
CLEARANCES
To ensure optimal performance a minimum of 30 inches
clearances required from the back, left and right sides of the
HPWH unit and any wall obstruction. A minimum of 36 inches
clearance on the front of the unit for access to the control box.
ELECTRICAL REQUIREMENTS
Ensure the power supply voltage and phase at the job site
matches the power supply ratings listed on the HPWH data
sticker label BEFORE INSTALLATION BEGINS.
The installation must conform with these instructions and the
local code authority having jurisdiction and the requirements
of the power company. In the absence of local codes,
the installation must comply with the current editions of
the National Electrical Code, ANSI/NFPA 70 or the Canadian
Electrical Code CSA C22.1.
Voltage applied to the HPWH should not vary more than +5%
to -10% of the voltage requirement listed on the HPWH rating
label for satisfactory operation.
TABLE 2 - VOLTAGE & AMPERAGE RATINGS
Model
Volts/Phase/HZ
Compressor
MCA
MOCP/MFS
LRA
RLA
WHP025
208-230/1/60
73
17.4
22
25
208-230/3/60
63
10.4
13
15
440-480/3/60
31
5.9
7
10
575/3/60
31
5.2
7
10
WHP060
208-230/1/60
129
30.1
38
40
208-230/3/60
156
22.1
28
30
440-480/3/60
75
11
14
15
575/3/60
54
9
11
15
WHP090
208-230/3/60
239
37.2
46
50
440-480/3/60
125
19.8
25
30
575/3/60
80
13.4
17
20
WHP125
208-230/3/60
300
53
65
70
440-480/3/60
150
26.7
33
35
575/3/60
109
23.5
29
30
WHP185
208-230/3/60
505
78
97
100
440-480/3/60
225
35
43
45
575/3/60
180
29.3
36
40
WHP250
208-230/3/60
446
92.7
116
125
440-480/3/60
223
46.7
59
60
575/3/60
164
38.9
49
50
LRA: Locked Rotor Amps
RLA: Rated Load Amps
MCA: Maximum Current Ampacity
MOCP: Minimum Overcurrent Protection