background image

11

6

Parameters 

(continued)

Changeable parameters

The following is a brief discussion of the changeable
parameters, their default settings, the range of adjustment,
and their location. The title for the parameters may differ
slightly from the PC to the boiler display. To prevent
confusion, the boiler display version will be listed in
parenthesis. 

Set 1: System setup

Set 1 is accessed by clicking on 

Parameters

at the top of the

Main Screen window (FIG. 6-1), then on 

Set 1: Control Setup

on the pull-down menu.

Ramp delay settings

When active, the ramp delay limits the boiler firing rate when
a SH cycle has started 

*

. There are 6 limiting steps used to

limit temperature overshoot and short cycles (see FIG. 6-2).
This feature can be turned on or off depending on the
installation. The default condition for this feature is disabled.
It should only be needed when the flow through the heat
exchanger is very low, or the flow in the primary loop can be
less than the flow in the secondary loop.  The time for each of
the 6 ramp delays as well as the power level for each of the 6
ramp delays are adjustable. The time range for each ramp
delay is adjustable from 1 minute to 40 minutes with the total
of all 6 ramp delays not to exceed 109 minutes. The default
delay time for Periods 1, 2, and 3 is 2 minutes.  The default
delay time for Periods 4, 5, and 6 is 1 minute. This process can
also work in reverse when the boiler shuts off.  After shutting
off, the max firing rate will be limited to the ramp 6 limit for
the period 6 time delay, then to the ramp 5 limit for the period
5 time delay, and so forth.  This step down feature overrides
the step up feature until the ramp up limit becomes higher
than the ramp down limit.  To access the Ramp Delay settings,
click on the tab labeled 1D Ramp Delay (see FIG. 6-2).

Figure 6-2

Parameter Set 1D

The power range for each ramp delay is adjustable from 0 to
100. The defaults for each ramp delay is ramp delay 1= 20%,
ramp delay 2=30%, ramp delay 3=40%, ramp delay 4=55%,
ramp delay 5=75%, ramp delay 6=100% (FIG. 6-3).  Note that
the limit in period 6 will limit the firing rate throughout the
entire call for heat.  The locations for these parameters are
1DG through 1DL.  See parameter 4FE (page 17 of this
manual) to enable or disable the ramp delay feature.

Figure 6-3

Ramp Delay Interval

PC Program Instructions

*

This is recommended for single-boiler installations only.

Summary of Contents for SMART TOUCH

Page 1: ...SYNC Installation and Operation Manual and the SYNC Service Manual before installing Perform steps in the order given Failure to comply could result in severe personal injury death or substantial pro...

Page 2: ...3 PC to Unit Connection 3 Starting the Program 4 6 2 Status Screen 5 6 3 Graphics Screen 7 4 Fault History Screen 8 5 Cascade Screen 9 6 PARAMETERS Parameter Information Screens 10 Changeable Paramet...

Page 3: ...r assigned to the USB cable above The programs display temperatures in F If you wish to display temperatures in C click on the Settings tab along the top of the Main Screen window and move the cursor...

Page 4: ...the upper left hand corner of the window A window opens in which you can type in the password see FIG 1 3 Note that the password is case sensitive and is in all CAPS Click on the Ok button or press th...

Page 5: ...o run at low fire Finally the 0 10Vdc input Voltage and Flame Current are shown To the right of the sensor temperature readings are the various setpoints The SH setpoint is the setpoint the SMART TOUC...

Page 6: ...active limits if any the last active limit the burner status the last fault and the date and time as stored in the SMART TOUCH PC Program Instructions While in the SMART TOUCH Status Screen you can g...

Page 7: ...he desired scale The top number represents F and the bottom number represents C Press the Ok button to close the Options window The background color of the Graphics Screen can be changed by pressing t...

Page 8: ...is shown as well as the number of successful and failed ignition attempts Finally a count of internal checks is shown The total number of occurrences of certain faults are also stored in the control a...

Page 9: ...t is a check box indicating if the temperature regulation is being held constant and if the Ramp Delay feature is active The Freeze P1 regulation box is checked when the next controller can be started...

Page 10: ...an adjustment to a parameter select the parameter to be changed from the appropriate set Click on the box next to the parameter and type in the value for the parameter Once an adjustment has been mad...

Page 11: ...stable The time range for each ramp delay is adjustable from 1 minute to 40 minutes with the total of all 6 ramp delays not to exceed 109 minutes The default delay time for Periods 1 2 and 3 is 2 minu...

Page 12: ...switching boiler on Parameter 2DJ is the minimum time delay between starting one burner and starting the next burner in the Cascade The range for this parameter is 0 seconds to 255 seconds The default...

Page 13: ...mperature setpoint for fixed operation or the maximum temperature setpoint when the outdoor air sensor is used This parameter can be changed by accessing parameter 4AA The temperature range of this pa...

Page 14: ...alue is 0 This feature will be active if this parameter is set to anything other than 0 Night setback temperature NSB Setp Once the internal clock has been set correctly the night setback feature can...

Page 15: ...has occurred or the maximum user setpoint has been reached Once the SH demand has been satisfied the setpoint will revert back to its calculated setting The boost temperature can be changed by accessi...

Page 16: ...ndow click on the tab labeled 4D Pump Delay to set the delay time for the boiler system and HW pumps see FIG 6 8 below Figure 6 8 Parameter Set 4D SH pump delay after SH demand Boiler Pump D This feat...

Page 17: ...re rises to or above this point the water temperature will be at its minimum setpoint This parameter can be changed by accessing parameter 4FD The temperature range of this parameter is 30 F 34 C to 9...

Page 18: ...eter 4GD The voltage range for this parameter is 0Vdc to 4GC The default value is 10Vdc Min BMS voltage to start demand BMS V Heat If parameter 4GK is set to 1 then the heat demand will be generated b...

Page 19: ...pear confirming that the file was saved Note that the new file name appears in the lower right hand corner of the SMART TOUCH PC program window BMS Voltage at min power BMS V min mod If parameter 4CB...

Page 20: ...Revision Notes Revision A initial release SYNC PCP Rev A Printed in the USA 4 10...

Reviews: