background image

13

PC Program Instructions

6

Parameters 

(continued)

Parameter 

2EB

sets the pump delay time for the boiler pump

after an over-temperature condition. This time is adjustable
from 0 minutes to 40 minutes. The default time is 2 minutes.

If the boiler pump or HW pump have not been active in a 24
hour period, the SMART TOUCH will activate the
appropriate pump for a programmed time to prevent
jamming.  The boiler pump time can be changed by accessing
parameter 

2EC

. This time is adjustable from 0 minutes to 40

minutes. The default time is 20 seconds.  The HW pump time
can be changed by accessing parameter 

2ED

. This time is

adjustable from 0 minutes to 40 minutes. The default time is
20 seconds. 

Set 4: Menu values

Set 4 contains parameters that can be accessed from the boiler
display. The parameters in this set control the basic operation
of the boiler.  To access these parameters, click on 

Parameters

at the top of the Main Screen window (FIG. 6-1, page 10),
then click on 

Set 4: Menu Values

on the pull-down menu

(FIG. 6-6).  

Figure 6-5

Parameter Set 2E

Figure 6-6

Parameter Set 4A

Space Heating (SH) user setpoint (User Setp)

The SH User Setpoint sets the water temperature setpoint for
fixed operation or the maximum temperature setpoint when the
outdoor air sensor is used. This parameter can be changed by
accessing parameter 

4AA

. The temperature range of this

parameter is 50°F to 190°F. The default value is 125°F.

SH min user setpoint (Min User Setp)

The SH Minimum User Setpoint sets the minimum water
temperature setpoint that can be used for space heating
operation. The user or installer will not be able to program the
control with a lower SH setpoint. This parameter can be
changed by accessing parameter 

4AB

. The temperature range of

this parameter is 0°F to 190°F. The default value is 70°F.

SH max user setpoint (Max User Setp)

The SH Maximum User Setpoint sets the maximum water
temperature setpoint that can be used for space heating. The
user or installer will not be able to program the control with a
higher SH setpoint. This parameter can be changed by accessing
parameter 

4AC

. The temperature range of this parameter is 0°F

to 190°F. The default value is 190°F.

SH turn-off differential (SH off df)

The SH Turn-off Differential sets how many degrees above the
Max. Cascade setpoint (parameter 

4AY

) the outlet temperature

has to go before the boiler will shut off. This parameter can be
changed by accessing parameter 

4AD

. The temperature range of

this parameter is 0°F to 86°F. The default value is 10°F.

Summary of Contents for SMART TOUCH

Page 1: ...SYNC Installation and Operation Manual and the SYNC Service Manual before installing Perform steps in the order given Failure to comply could result in severe personal injury death or substantial pro...

Page 2: ...3 PC to Unit Connection 3 Starting the Program 4 6 2 Status Screen 5 6 3 Graphics Screen 7 4 Fault History Screen 8 5 Cascade Screen 9 6 PARAMETERS Parameter Information Screens 10 Changeable Paramet...

Page 3: ...r assigned to the USB cable above The programs display temperatures in F If you wish to display temperatures in C click on the Settings tab along the top of the Main Screen window and move the cursor...

Page 4: ...the upper left hand corner of the window A window opens in which you can type in the password see FIG 1 3 Note that the password is case sensitive and is in all CAPS Click on the Ok button or press th...

Page 5: ...o run at low fire Finally the 0 10Vdc input Voltage and Flame Current are shown To the right of the sensor temperature readings are the various setpoints The SH setpoint is the setpoint the SMART TOUC...

Page 6: ...active limits if any the last active limit the burner status the last fault and the date and time as stored in the SMART TOUCH PC Program Instructions While in the SMART TOUCH Status Screen you can g...

Page 7: ...he desired scale The top number represents F and the bottom number represents C Press the Ok button to close the Options window The background color of the Graphics Screen can be changed by pressing t...

Page 8: ...is shown as well as the number of successful and failed ignition attempts Finally a count of internal checks is shown The total number of occurrences of certain faults are also stored in the control a...

Page 9: ...t is a check box indicating if the temperature regulation is being held constant and if the Ramp Delay feature is active The Freeze P1 regulation box is checked when the next controller can be started...

Page 10: ...an adjustment to a parameter select the parameter to be changed from the appropriate set Click on the box next to the parameter and type in the value for the parameter Once an adjustment has been mad...

Page 11: ...stable The time range for each ramp delay is adjustable from 1 minute to 40 minutes with the total of all 6 ramp delays not to exceed 109 minutes The default delay time for Periods 1 2 and 3 is 2 minu...

Page 12: ...switching boiler on Parameter 2DJ is the minimum time delay between starting one burner and starting the next burner in the Cascade The range for this parameter is 0 seconds to 255 seconds The default...

Page 13: ...mperature setpoint for fixed operation or the maximum temperature setpoint when the outdoor air sensor is used This parameter can be changed by accessing parameter 4AA The temperature range of this pa...

Page 14: ...alue is 0 This feature will be active if this parameter is set to anything other than 0 Night setback temperature NSB Setp Once the internal clock has been set correctly the night setback feature can...

Page 15: ...has occurred or the maximum user setpoint has been reached Once the SH demand has been satisfied the setpoint will revert back to its calculated setting The boost temperature can be changed by accessi...

Page 16: ...ndow click on the tab labeled 4D Pump Delay to set the delay time for the boiler system and HW pumps see FIG 6 8 below Figure 6 8 Parameter Set 4D SH pump delay after SH demand Boiler Pump D This feat...

Page 17: ...re rises to or above this point the water temperature will be at its minimum setpoint This parameter can be changed by accessing parameter 4FD The temperature range of this parameter is 30 F 34 C to 9...

Page 18: ...eter 4GD The voltage range for this parameter is 0Vdc to 4GC The default value is 10Vdc Min BMS voltage to start demand BMS V Heat If parameter 4GK is set to 1 then the heat demand will be generated b...

Page 19: ...pear confirming that the file was saved Note that the new file name appears in the lower right hand corner of the SMART TOUCH PC program window BMS Voltage at min power BMS V min mod If parameter 4CB...

Page 20: ...Revision Notes Revision A initial release SYNC PCP Rev A Printed in the USA 4 10...

Reviews: