background image

17

PC Program Instructions

6

Parameters 

(continued)

Figure 6-10

Parameter Set 4F

OA reset water temp at min outdoor temp (4FC) (Reset
T Lo Out)

When the outdoor air temperature drops to its minimum
setting (

4FC

), the water temperature setpoint will be at this

value.  However, if the SH user setpoint (

4AA

) is lower, it will

override this setting.  If the SH user setpoint is higher, the water
temperature setpoint will continue to climb as the outdoor
temperature drops below 

4FC.

This parameter can be changed

by accessing parameter 

4FA

. The temperature range of this

parameter is 0°F (-18°C) to 190°F. (88 °C).  The default value is
180°F (82°C), (FIG 6-11, page 18).

OA reset water temp at max outdoor temp (4FD)
(Reset T Hi Out)

When the outdoor air temperature rises to or above its
maximum setting (

4FD

), the water temperature setpoint will be

at this value. This parameter can be changed by accessing
parameter 

4FB

. The temperature range of this parameter is 0°F

(-18°C) to 190°F (88°C).  The default value is 70°F (21°C), (FIG
6-11, page 18).

OA reset outdoor temp at max water temp (4FA) (Out
T Hi Reset)

When the outdoor air temperature drops to this point, the water
temperature setpoint will be at the setting given by parameter

4FA

(if not overridden by the SH user setpoint). This parameter

can be changed by accessing parameter 

4FC

. The temperature

range of this parameter is -30°F (-34°C) to 90°F (32°C).  The
default value is 25°F (-4°C), (FIG 6-11, page 18).

OA reset outdoor temp at min water temp (4FB) (Out
T Lo Reset)

When the outdoor air temperature rises to or above this point,
the water temperature will be at its minimum setpoint. This
parameter can be changed by accessing parameter 

4FD

. The

temperature range of this parameter is -30°F (-34°C) to 90°F
(32°C). The default value is 70°F (21°C), (FIG. 6-11, page 18).

Ramp delay (Ramp delay)

This parameter configures the ramp delay feature from off to
on. This parameter can be changed by accessing parameter 

4FE

(FIG. 6-10). The control range of this parameter is 0 = Off,
1 = Ramp Up Only, and 2 = Ramp Up and Ramp Down. The
default is 0.

No. of months for service reminder (Serv Not time)

When the boiler control determines that a scheduled service
is due based on days of installation, the boiler display will
show a “Maintenance Required” screen.  This parameter is
adjustable by accessing parameter 

4EA

. The time range for

this parameter is 0 months to 36 months. The default time is
12 months.

Running hours for service reminder (Serv Not Run h)

When the boiler control determines that a scheduled service
is due based on the hours of actual operation, the boiler
display will show a “Maintenance Required” screen.  This
parameter is adjustable by accessing parameter 

4EB

. The time

range for this parameter is 0 hours to 100,000 hours. The
default time is 10,000 hours.

Burner cycles for service reminder (Serv Not cycl)

When the boiler control determines that a scheduled service
is due based on the number of boiler cycles, the boiler display
will show a “Maintenance Required” screen.  This parameter
is adjustable by accessing parameter 

4EC

. The range for this

parameter is 0 cycles to 100,000 cycles. The default is 10,000
cycles.

To adjust the Outdoor Air Reset curve, click on the tab labeled

4F OA Reset Curve

(see FIG. 6-10 below).

Summary of Contents for SMART TOUCH

Page 1: ...SYNC Installation and Operation Manual and the SYNC Service Manual before installing Perform steps in the order given Failure to comply could result in severe personal injury death or substantial pro...

Page 2: ...3 PC to Unit Connection 3 Starting the Program 4 6 2 Status Screen 5 6 3 Graphics Screen 7 4 Fault History Screen 8 5 Cascade Screen 9 6 PARAMETERS Parameter Information Screens 10 Changeable Paramet...

Page 3: ...r assigned to the USB cable above The programs display temperatures in F If you wish to display temperatures in C click on the Settings tab along the top of the Main Screen window and move the cursor...

Page 4: ...the upper left hand corner of the window A window opens in which you can type in the password see FIG 1 3 Note that the password is case sensitive and is in all CAPS Click on the Ok button or press th...

Page 5: ...o run at low fire Finally the 0 10Vdc input Voltage and Flame Current are shown To the right of the sensor temperature readings are the various setpoints The SH setpoint is the setpoint the SMART TOUC...

Page 6: ...active limits if any the last active limit the burner status the last fault and the date and time as stored in the SMART TOUCH PC Program Instructions While in the SMART TOUCH Status Screen you can g...

Page 7: ...he desired scale The top number represents F and the bottom number represents C Press the Ok button to close the Options window The background color of the Graphics Screen can be changed by pressing t...

Page 8: ...is shown as well as the number of successful and failed ignition attempts Finally a count of internal checks is shown The total number of occurrences of certain faults are also stored in the control a...

Page 9: ...t is a check box indicating if the temperature regulation is being held constant and if the Ramp Delay feature is active The Freeze P1 regulation box is checked when the next controller can be started...

Page 10: ...an adjustment to a parameter select the parameter to be changed from the appropriate set Click on the box next to the parameter and type in the value for the parameter Once an adjustment has been mad...

Page 11: ...stable The time range for each ramp delay is adjustable from 1 minute to 40 minutes with the total of all 6 ramp delays not to exceed 109 minutes The default delay time for Periods 1 2 and 3 is 2 minu...

Page 12: ...switching boiler on Parameter 2DJ is the minimum time delay between starting one burner and starting the next burner in the Cascade The range for this parameter is 0 seconds to 255 seconds The default...

Page 13: ...mperature setpoint for fixed operation or the maximum temperature setpoint when the outdoor air sensor is used This parameter can be changed by accessing parameter 4AA The temperature range of this pa...

Page 14: ...alue is 0 This feature will be active if this parameter is set to anything other than 0 Night setback temperature NSB Setp Once the internal clock has been set correctly the night setback feature can...

Page 15: ...has occurred or the maximum user setpoint has been reached Once the SH demand has been satisfied the setpoint will revert back to its calculated setting The boost temperature can be changed by accessi...

Page 16: ...ndow click on the tab labeled 4D Pump Delay to set the delay time for the boiler system and HW pumps see FIG 6 8 below Figure 6 8 Parameter Set 4D SH pump delay after SH demand Boiler Pump D This feat...

Page 17: ...re rises to or above this point the water temperature will be at its minimum setpoint This parameter can be changed by accessing parameter 4FD The temperature range of this parameter is 30 F 34 C to 9...

Page 18: ...eter 4GD The voltage range for this parameter is 0Vdc to 4GC The default value is 10Vdc Min BMS voltage to start demand BMS V Heat If parameter 4GK is set to 1 then the heat demand will be generated b...

Page 19: ...pear confirming that the file was saved Note that the new file name appears in the lower right hand corner of the SMART TOUCH PC program window BMS Voltage at min power BMS V min mod If parameter 4CB...

Page 20: ...Revision Notes Revision A initial release SYNC PCP Rev A Printed in the USA 4 10...

Reviews: